Troubleshooting
Electrical Control System
245
2.4.3.8. E8 malfunction
E8 display
Outdoor fan speed has been out of control
Shut off the power supply and
turn it on 5 seconds later. Is it
still displaying the error code?
Shut off the power supply,
rotate the fan by hand. Does
it rotate properly?
The unit operates normally.
Replace outdoor fan
motor.
Check the wires of fan motor.
Are all the connections good?
No
Yes
No
Correct the connections.
No
Yes
Replace indoor main PCB. Is it
still displaying the error code?
Yes
Yes
Check the voltage between port
1 and 3 of fan motor connector,
is it within 140V~380V?
No
DC motor voltage input and output
NO.
Color
Signal
Voltage
1
Red
Vs/Vm
140
~
380V
2
---
---
---
3
Black
GND
0V
4
White
Vcc
13.5~16.5V
5
Yellow
Vsp
0~6.5V
6
Blue
FG
15V