Troubleshooting
244
Electrical Control System
2.4.3.7. E6 malfunction (For 36K 1-phase models)
E6 display
PFC module protection
Check whether the
connecting line between
main board and the PFC
module is connected tightly
Yes
Check whether the voltage
range of P-N on IPM
module is normal?
DC277-
410V
No
Check
whether
the
inductance of PFC module
is good? If the inductance is
good, the resistance of the
two ports is 0
Yes
Replace the inductance
No
Connect it tightly, check
normal or not
Replace the outdoor main board
Yes
Yes
No
No
Replace the PFC module
Trouble is solved