Electrical Control Function
Electrical Control System
215
For CBD012
In cooling mode, indoor fan runs all the time and the speed can be selected as high, medium, low, auto and
silent.
The auto fan:
3.5
3.0
High
Low
1.0
Medium
1.5
For other models:
5.0
4.0
High
Low
2.0
Medium
3.0
1.3.2.4 Evaporator low temperature T2 protection.
For 12K models
:
---T2<0
℃
, the compressor will stop and restart when T2
>=
5
℃
.
---0
℃
≦
T2<4
℃
, the compressor frequency will be limited and decreased to the lower level
---4
℃
≤T2<7
℃
, the compressor will keep the current frequency.
---T2>7
℃
, the compressor frequency will not be limited.
For FWDB18/024
- When T2<2
℃
and lasts for 3 minutes, the indoor has no capacity demand and resume till T2
≥
7
℃
.
- When set point <17
℃
,and the T2<7
℃
, the indoor fan will be forced to run the speed RAFANC6 (1200
rpm for FWDB18, 1350rpm for FWDB24) till the T2>10
℃
For other models: When T2<2
℃
and lasts for 3 minutes, the indoor has no capacity demand and resume till
T2
≥
7
℃
.
1.3.2.5 Condenser high temperature T3 protection
For 12K models :
---55
℃
<T3<60
℃
, the compressor frequency will decrease to the lower level until to F1 and then runs at F1.If
T3<55
℃
, the compressor will keep running at the current frequency.
---T3<52
℃
, the compressor will not limit the frequency and resume to the former frequency.
Summary of Contents for AWAU-YLD012-H11
Page 14: ...Dimensions Console Type 135 2 Dimensions AWSI XAD012 N11 AWSI XAD018 N11 ...
Page 15: ...Service Space 136 Console Type 3 Service Space ...
Page 16: ...Wiring Diagrams Console Type 137 4 Wiring Diagrams AWSI XAD012 N11 AWSI XAD018 N11 ...
Page 21: ...Field Wiring 142 Console Type 10 Field Wiring AWSI XAD012 N11 AWSI XAD018 N11 ...
Page 31: ...Wiring Diagrams 152 Outdoor Units 4 Wiring Diagrams AWAU YLD012 H11 ...
Page 33: ...Wiring Diagrams 154 Outdoor Units AWAU YLD036 H13 AWAU YLD048 H13 ...
Page 34: ...Wiring Diagrams Outdoor Units 155 AWAU YLD060 H13 ...