background image

En-11

Operation behavior

Each input terminal works as follows.

Connector

Input signal

Status

Input1
CN131 (Yellow)

OFF

Normal operation

ON

Low noise mode operation

Input2
CN132 (Green) *1

OFF

Cooling priority

ON

Heating priority

Input3
CN133 (White)

OFF

Normal operation

ON

Outdoor unit operation peak control

Input4
CN134 (Red)

OFF

Normal operation

ON

Batch stop or Emergency stop operation *2, *3

Input5
CN135 (Orange) *4

No pulse

No information from electricity meter

Pulse

Power usage information from electricity meter

The operations of each input terminal and the selection of function are set with the push 
button on the PC board of outdoor unit. About the setting, please refer to “7. 4. Push button 
setting”.

NOTE:

*1:  The “external input priority mode” must be set by pressing push button on PC board 

of outdoor unit. (Refer to “7. FIELD SETTING”.)

*2:  Batch stop or Emergency stop pattern can be selected by outdoor unit PC board 

push button. (Refer to “7. FIELD SETTING”.)

*3:  The emergency stop function mounted in the J-II does not guarantee the regulations 

of each country. For this reason, suf

fi

 cient checking is necessary regarding use. 

Especially, since the fact that the equipment may not be emergency-stopped in the 
case of breaking of the wiring to the external input terminals and communication 
line, communication error due to noise, VRF external input circuit trouble, etc. must 
be considered, the provision of double measures that add direct interruption of the 
power supply by switch, etc. is recommended as a precaution.

*4:  Pulse input to CN135 must be width 50 ms or more, and must be interval 50 ms or 

more.

6.6.3  External output terminal

You can detect the operation condition of outdoor unit and the abnormal situation of both 
indoor and outdoor unit.
Wiring method and speci

fi

 cations

Error status

This output indicates the outdoor unit 
and connected indoor unit's “Normal” or 
“Error” status.

Operation status

This output indicates the outdoor unit's 
“Operation” status.

Connector

Output 

voltage

Status

Output1
CN136 
(Black)

0V

Normal

DC 12-24 V 

*5

Error

Output2
CN137 
(Blue)

0V

Stop

DC 12-24 V 

*5

Operation

P.C.B

*7

*5

*6

CN136 (Black) or 
CN137 (Blue)

DC power supply 
(External) 12-24 V

Connected load (Operation Indica-
tor or Error Indicator)

Connected unit

*5: Provide a DC 12 to 24 V power supply. 

Select a power supply capacity with an ample surplus for the connected load.

*6: The allowable current is 30 mA or less. 

Provide a load resistance such that the current becomes 30 mA or less.

*7:  Polarity is [+] for pin 1 and [-] for pin 2. Connect correctly.

Do not impress a voltage exceeding 24 V across pins 1-2.

*  A twisted pair cable (0.33 mm² (22AWG)) should be used. 

Maximum length of cable is 150 m.

*  Use an external input and output cable with appropriate external dimension, depending 

on the number of cables to be installed.

6.6.4  Base heater terminal

This is the output signal for base heater. Output signal ON, when the outdoor temperature 
goes down below 2°C, and signal OFF at the outdoor temperature 4°C.

  

Voltage: 

power supply input voltage

cable

(0.82 mm

2

 (18AWG))

P.C.B.

Base heater *9

CN115 

(Black)

*8

*8:  Connect to pin 1 and pin 3. No connection pin 2 and pin 4.
*9: The allowable current is 1 A or less.

7. FIELD 

SETTING

CAUTION

Discharge the static electricity from your body before setting up the DIP switches.
Never touch the terminals or the patterns on the parts that are mounted on the PC 
board.

7.1.  Field setting switches

Remove the service panel of the outdoor unit and the cover of the electrical component 
box to access the PC board of the outdoor unit.
PC board switches for various settings and LED displays are shown in the 

fi

 gure.

7.2.  DIP switch setting

7.2.1  List of Settings

SET 5 must be set for the DIP 
switch.
Con

fi

 gure the settings before turn-

ing on the power. Settings for SET 
1, SET 2, SET 3 and SET 4 DIP 
switches are factory default ones. Do 
not change them.

DIP Switch

Function

SET 1

1-4

Forbidden

SET 2

1-4

Forbidden

SET 3

1-4

Forbidden

SET 4

1-4

Forbidden

SET 5

1-3

Forbidden

4

Terminal resistor setting

7 Segment display

Push button

LED lamp

Rotary switch

Outdoor unit printed circuit board

DIP switch

DIP switch

7.2.2  Terminating resistor setting

CAUTION

Be sure to set the terminal resistor according to speci

fi

 cations.

Set the terminal resistor for every network segment (NS).

If terminal resistor is set in multiple devices, the overall communication system may be 
damaged.
If terminal resistor is not set in a device, abnormal communication may occur.

•  Be sure to set 1 terminal resistor in a network segment. You can set the terminal resistor 

at the outdoor unit or signal ampli

fi

 er.

•  When setting the terminal resistor of a signal ampli

fi

 er, refer to the installation manual of 

the signal ampli

fi

 er.

•  When setting multiple terminal resistors, take note of the following items.

1

 How many network segments are there in a VRF system?

2

 Where will you set the terminal resistors in a network segment? (Condition for 1 seg-

ment: Total number of outdoor and indoor units and signal ampli

fi

 ers is less than 64, or 

the total length of the transmission cable is less than 500 m)

3

 How many outdoor units are connected to 1 refrigerant system?

Con

fi

 gure the setting (DIP switch SET 5) 

of the terminal resistor of the outdoor units 
as shown below from conditions 

1

 to 

3

.

SET 5

Terminal 

resistor

Remarks

4

OFF

Disable

ON

Enable

(Factory setting)

Figure: Terminal resistor setting

NS2 (Network 
segment 2)

NS3 (Network segment 3)

NS4 (Network 
segment 4)

NS1 (Network segment 1)
(Set terminal resistor at outdoor units)

Master unit

Master unit

Master unit

Refrigerant system 1

Refrigerant system 2

Refrigerant system 3

Terminal resistor: off

Terminal resistor: on

Terminal resistor: on

About the setting of 
terminal resistor

Outdoor unit

Install

Do not 
install

: On

: Off

Signal ampli

fi

 er

9380545170_IM.indb   11

9380545170_IM.indb   11

5/19/2016   2:23:17 PM

5/19/2016   2:23:17 PM

Summary of Contents for AJH040LBLAH

Page 1: ... DIŞ ÜNİTE For authorized service personnel only Nur für autorisiertes Fachpersonal Uniquement réservé aux techniciens agréés Sólo para personal de servicio autorizado A uso esclusivo del personale tecnico autorizzato Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό Apenas para técnicos de assistência autorizados Только для авторизованного обслуживающего персонала Yalnızca yetkili servis personeli için ...

Page 2: ...c shock or fire Securely install the electrical box cover on the unit An improperly installed electrical box cover can cause serious accidents such as electric shock or fire through exposure to dust or water Do not turn ON the power until all work has been completed Turning ON the power before the work is completed can cause serious accidents such as electric shock or fire After the installation m...

Page 3: ...n or water leakage When setting it up near the equipment that generates electromagnetic waves and the equipment that generates the higher harmonics wave be sure to take measures against noise Otherwise it may cause malfunction or failure When energizing to the crankcase heater please turn on the power 12 hours or earlier before operation begins When the energizing time is short it may cause failur...

Page 4: ...e installed more than 1 meter apart you could still receive noise under some signal conditions Keep the length of the piping of the indoor and outdoor units within the allowable range For maintenance purposes do not bury the piping 3 2 Drain processing CAUTION Perform drain work in accordance with this Manual and ensure that the drain water is properly drained If the drain work is not carried out ...

Page 5: ...of the unit Otherwise the suction grilles on the sides of the unit may be deformed Front view Rear view Fig B Handle Handle Suction grille Fig A 3 5 Installing the unit Please install the outdoor unit without slant within 3 degrees Install 4 anchor bolts at the locations indicated with arrows in the figure To reduce vibration do not install the unit directly on the ground Install it on a secure ba...

Page 6: ...n method Outdoor 1 month or more Pinch pipes Less than 1 month Pinch or tape pipes Indoor Pinch or tape pipes Protect the pipes to prevent the entry of moisture and dust Especially pay attention when passing the pipes through a hole or connecting the end of a pipe to the outdoor unit 4 SYSTEM CONFIGURATION 4 1 System configuration CAUTION Always keep to the limit on the total amount of refrigerant...

Page 7: ...ontal line View D View C Horizontal line Vertical line Gas pipe Liquid pipe Outdoor unit side Outdoor unit side H1 0 to 10 mm H2 0 to 10 mm α1 0 to 1 β1 10 to 10 α2 0 to 1 β2 10 to 10 PROHIBITED CAUTION Do not connect a separation tube after a header Leave the distance 0 5 m or more for straight part to branch tube and header Main pipe 0 5 m or more To indoor unit To indoor unit To indoor unit Mai...

Page 8: ...ve any burrs 3 Insert the flare nut always use the flare nut attached to the indoor and outdoor units respectively onto the pipe and perform the flare processing with a flare tool Leakage of refrigerant may result if other flare nuts are used 4 Protect the pipes by pinching them or with tape to prevent dust dirt or water from entering the pipes L Check if L is flared uniformly and is not cracked o...

Page 9: ...breaker is too high the amperage at which the breaker cuts out may decrease Use a breaker Included with earth leakage circuit breaker that is capable of handling high frequencies Because the outdoor unit is inverter controlled a high frequency earth leakage circuit breaker is necessary to prevent a malfunction of the breaker itself When the electrical switchboard is installed outdoors place it und...

Page 10: ...g 2 NOTE Do not use loop wiring This may lead to parts damage and erroneous operation Outdoor unit Indoor unit Signal Amplifier System Controller Touch Panel Controller Transmission line Terminal resistor Terminal resistor NS 1 NS 2 F H L G K J E 6 4 3 Enabling Disabling automatic address setting You can enable disable automatic address setting for the indoor unit and the signal ampli fier To enab...

Page 11: ...rminal Sleeve Screw with special washer Ring terminal Cable Shielding the transmission cable Connect both ends of the shielded wire of the transmission cable to the earth ground terminal of the equipment or to the earth ground screw near the terminal Be sure to use one side of a twisted pair cable when using transmission cable with 2 sets of twisted pair cables Wind with insulation tape to prevent...

Page 12: ... This is the output signal for base heater Output signal ON when the outdoor temperature goes down below 2 C and signal OFF at the outdoor temperature 4 C Voltage power supply input voltage cable 0 82 mm2 18AWG P C B Base heater 9 CN115 Black 8 8 Connect to pin 1 and pin 3 No connection pin 2 and pin 4 9 The allowable current is 1 A or less 7 FIELD SETTING CAUTION Discharge the static electricity ...

Page 13: ...efrigerant circuit address Rotary Switch Setting Setting Setting range Type of switch REF AD 10 1 Refrigerant circuit address 0 99 Setting example 63 0 0 0 1 0 1 2 0 2 REF AD 10 REF AD 1 Rotary Switch REF AD 1 Factory setting 0 Rotary Switch REF AD 10 Factory setting 0 98 9 8 99 9 9 7 4 Push button setting Various functions can be set Set when necessary Perform settings after all indoor units have...

Page 14: ...s Last 2 digits When F3 to F9 are displayed continue to press the SELECT button until F2 is displayed 2 Setting the first 2 digits 3 Setting the last 2 digits Continue to press the SELECT button until the desired number appears at the last 2 digits Every press of the SELECT button will change the setting number for the first 2 digits Continue to press the SELECT button until the desired number app...

Page 15: ...e 7 segment display When ERROR is displayed inspect the units Use the MODE EXIT SELECT and ENTER buttons on the outdoor unit PC board to configure settings according to the procedures below 1 Function setting The display when the main power is turned on When F4 to F9 are displayed continue to press the SELECT button until F3 is displayed Press the SELECT button until 11 is displayed Press the ENTE...

Page 16: ...uation procedure 1 Remove the blank caps of the gas pipe and liquid pipe and check that the valves are closed 2 Remove the charging port cap 3 Connect a vacuum pump and a pressure gauge to a charging hose and connect it to the charging port 4 Activate the vacuum pump and vacuum the indoor unit and connection piping until the pressure gauge becomes 100 7 kPa 755mm Hg Evacuate from both the gas pipe...

Page 17: ... has condensed in the 3 way valve of the outdoor unit could travel to the indoor unit Therefore use putty in the space between the pipe and the insulation to prevent the entry of water to the indoor units Fig A Putty Insulation 9 TEST RUN 9 1 Indoor unit connection check Normal operation will not be possible without performing the Indoor unit connection check 9 1 1 Things to confirm before startin...

Page 18: ...he EN TER button for more than 3 seconds 2 When errors other than the address of the overlap indoor unit exist press SE LECT button to switch to the next error If error occurs it will display Ad address number 9 2 Test run Before the test operation check the following items 1 Is there a gas leakage At pipe connections flange connections and brazed areas 2 Is the system charged with the specified v...

Page 19: ...r E 8 3 2 Outdoor unit liquid pipe temp thermistor 2 error E 8 4 1 Outdoor unit current sensor 1 error permanent stop E 8 6 1 Outdoor unit discharge pressure sensor error E 8 6 3 Outdoor unit suction pressure sensor error E 8 6 4 Outdoor unit high pressure switch 1 error Outdoor unit actuator error E 9 3 1 Outdoor unit inverter compressor start up error E 9 4 1 Outdoor unit trip detection E 9 5 5 ...

Reviews: