background image

En-4

3.3.1  Single outdoor unit installation

When the upward area is open 

(Unit: mm)

(1) Obstacles 

at 

rear 

only

150

(2)  Obstacles at rear and sides only

200

300

200

(3) Obstacles 

at 

front 

only

1000 or more

(4)  Obstacles at front and rear only

1000 or more

150

When an obstruction is present also in the upward area 

(Unit: mm)

(1)  Obstacles at rear and above only

300

Max. 500

1000

(2)  Obstacles at rear, sides, and above only

1500

250

250

500

Max. 500

3.3.2  Multiple outdoor unit installation

•  Provide at least 25 mm of space between the outdoor units if multiple units are installed.
•  When routing the piping from the side of an outdoor unit, provide space for the piping.
•  No more than 3 units must be installed side by side.

When 3 units or more are arranged in a line, provide the space as shown in the following 
example when an obstruction is present also in the upward area.

When the upward area is open 

(Unit: mm)

(1) Obstacles 

at 

rear 

only

300

(2) Obstacles 

at 

front 

only

1500 or more

(3)  Obstacles at front and rear only

500

1500 or more

When an obstruction is present also in the upward area 

(Unit: mm)

•  Obstacles at rear and above only

1500

500

Max. 300

1500

3.3.3  Outdoor units installation in multi row

*  The following settings are not recommended in case of cooling by a low outside tem-

perature.

 

(Unit: mm)

(1) Single 

parallel 

unit 

arrangement

(2) Multiple 

parallel 

unit 

arrangement

150

600

1000

2000 or 
more

500

600

1500

3000 or 
more

3.4.  Transporting the unit

WARNING

Do not touch the 

fi

 ns. Otherwise, personal injury could result.

CAUTION

When carrying the unit, hold the handles on the right and left sides and be careful.
If the outdoor unit is carried from the bottom, hands or 

fi

 ngers may be pinched.

•  Carry slowly in the manner as shown on “Fig. B” holding the handles “Fig. A” in right and 

left sides. (Be careful not to touch with hands or objects.)

•  Be sure to hold the handles on the sides of the unit. Otherwise, the suction grilles on the 

sides of the unit may be deformed.

Front view

Rear view

Fig. B

Handle

Handle

Suction grille

Fig. A

3.5.  Installing the unit

•  Please install the outdoor unit without slant. (within 3 degrees )
•  Install 4 anchor bolts at the locations indicated with arrows in the 

fi

 gure.

•  To reduce vibration, do not install the unit directly on the ground. Install it on a secure 

base (such as concrete blocks).

•  The foundation shall support the legs of the unit and have a width of 50 mm or more.
•  Depending on the installation conditions, the outdoor unit may spread its vibration during 

operation, which may cause noise and vibration. Therefore, attach damping materials 
(such as damping pads) to the outdoor unit during installation.

•  Install the foundation, making sure that there is enough space for installing the connec-

tion pipes.

•  Secure the unit to a solid block using foundation bolts. (Use 4 sets of commercially avail-

able M10 bolts, nuts, and washers.)

•  The bolts should protrude 20 mm. (Refer to the 

fi

 gure.)

•  If overturning prevention is required, purchase the necessary commercially available 

items.

166

AIR

650

154

50

50

16

20

410

Unit: mm

Bolt

Nut

Base

Do not install directly on the ground, this may result in equipment failure.
Provide ample space for ice buildup from condensate between the bottom of the unit and 
the 

fl

 at surface on which it is mounted.

Otherwise, there is risk that the drainage water will freeze between the device and the 
surface, disabling drainage.

Base

CAUTION

If the unit is installed in a region that is exposed 
to high winds, freezing conditions, freezing rain, 
snow fall or heavy snow accumulation, take 
appropriate measures to protect it from those ele-
ments.
To ensure stable operation, the outdoor unit must 
be installed on a raised stand or rack, at or above 
the anticipated snow depth for the region.
The installation of snow hoods and drift preven-
tion fencing is recommended when blowing and 
drifting snow is common to the region.

9380545170_IM.indb   4

9380545170_IM.indb   4

5/19/2016   2:23:16 PM

5/19/2016   2:23:16 PM

Summary of Contents for AJH040LBLAH

Page 1: ... DIŞ ÜNİTE For authorized service personnel only Nur für autorisiertes Fachpersonal Uniquement réservé aux techniciens agréés Sólo para personal de servicio autorizado A uso esclusivo del personale tecnico autorizzato Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό Apenas para técnicos de assistência autorizados Только для авторизованного обслуживающего персонала Yalnızca yetkili servis personeli için ...

Page 2: ...c shock or fire Securely install the electrical box cover on the unit An improperly installed electrical box cover can cause serious accidents such as electric shock or fire through exposure to dust or water Do not turn ON the power until all work has been completed Turning ON the power before the work is completed can cause serious accidents such as electric shock or fire After the installation m...

Page 3: ...n or water leakage When setting it up near the equipment that generates electromagnetic waves and the equipment that generates the higher harmonics wave be sure to take measures against noise Otherwise it may cause malfunction or failure When energizing to the crankcase heater please turn on the power 12 hours or earlier before operation begins When the energizing time is short it may cause failur...

Page 4: ...e installed more than 1 meter apart you could still receive noise under some signal conditions Keep the length of the piping of the indoor and outdoor units within the allowable range For maintenance purposes do not bury the piping 3 2 Drain processing CAUTION Perform drain work in accordance with this Manual and ensure that the drain water is properly drained If the drain work is not carried out ...

Page 5: ...of the unit Otherwise the suction grilles on the sides of the unit may be deformed Front view Rear view Fig B Handle Handle Suction grille Fig A 3 5 Installing the unit Please install the outdoor unit without slant within 3 degrees Install 4 anchor bolts at the locations indicated with arrows in the figure To reduce vibration do not install the unit directly on the ground Install it on a secure ba...

Page 6: ...n method Outdoor 1 month or more Pinch pipes Less than 1 month Pinch or tape pipes Indoor Pinch or tape pipes Protect the pipes to prevent the entry of moisture and dust Especially pay attention when passing the pipes through a hole or connecting the end of a pipe to the outdoor unit 4 SYSTEM CONFIGURATION 4 1 System configuration CAUTION Always keep to the limit on the total amount of refrigerant...

Page 7: ...ontal line View D View C Horizontal line Vertical line Gas pipe Liquid pipe Outdoor unit side Outdoor unit side H1 0 to 10 mm H2 0 to 10 mm α1 0 to 1 β1 10 to 10 α2 0 to 1 β2 10 to 10 PROHIBITED CAUTION Do not connect a separation tube after a header Leave the distance 0 5 m or more for straight part to branch tube and header Main pipe 0 5 m or more To indoor unit To indoor unit To indoor unit Mai...

Page 8: ...ve any burrs 3 Insert the flare nut always use the flare nut attached to the indoor and outdoor units respectively onto the pipe and perform the flare processing with a flare tool Leakage of refrigerant may result if other flare nuts are used 4 Protect the pipes by pinching them or with tape to prevent dust dirt or water from entering the pipes L Check if L is flared uniformly and is not cracked o...

Page 9: ...breaker is too high the amperage at which the breaker cuts out may decrease Use a breaker Included with earth leakage circuit breaker that is capable of handling high frequencies Because the outdoor unit is inverter controlled a high frequency earth leakage circuit breaker is necessary to prevent a malfunction of the breaker itself When the electrical switchboard is installed outdoors place it und...

Page 10: ...g 2 NOTE Do not use loop wiring This may lead to parts damage and erroneous operation Outdoor unit Indoor unit Signal Amplifier System Controller Touch Panel Controller Transmission line Terminal resistor Terminal resistor NS 1 NS 2 F H L G K J E 6 4 3 Enabling Disabling automatic address setting You can enable disable automatic address setting for the indoor unit and the signal ampli fier To enab...

Page 11: ...rminal Sleeve Screw with special washer Ring terminal Cable Shielding the transmission cable Connect both ends of the shielded wire of the transmission cable to the earth ground terminal of the equipment or to the earth ground screw near the terminal Be sure to use one side of a twisted pair cable when using transmission cable with 2 sets of twisted pair cables Wind with insulation tape to prevent...

Page 12: ... This is the output signal for base heater Output signal ON when the outdoor temperature goes down below 2 C and signal OFF at the outdoor temperature 4 C Voltage power supply input voltage cable 0 82 mm2 18AWG P C B Base heater 9 CN115 Black 8 8 Connect to pin 1 and pin 3 No connection pin 2 and pin 4 9 The allowable current is 1 A or less 7 FIELD SETTING CAUTION Discharge the static electricity ...

Page 13: ...efrigerant circuit address Rotary Switch Setting Setting Setting range Type of switch REF AD 10 1 Refrigerant circuit address 0 99 Setting example 63 0 0 0 1 0 1 2 0 2 REF AD 10 REF AD 1 Rotary Switch REF AD 1 Factory setting 0 Rotary Switch REF AD 10 Factory setting 0 98 9 8 99 9 9 7 4 Push button setting Various functions can be set Set when necessary Perform settings after all indoor units have...

Page 14: ...s Last 2 digits When F3 to F9 are displayed continue to press the SELECT button until F2 is displayed 2 Setting the first 2 digits 3 Setting the last 2 digits Continue to press the SELECT button until the desired number appears at the last 2 digits Every press of the SELECT button will change the setting number for the first 2 digits Continue to press the SELECT button until the desired number app...

Page 15: ...e 7 segment display When ERROR is displayed inspect the units Use the MODE EXIT SELECT and ENTER buttons on the outdoor unit PC board to configure settings according to the procedures below 1 Function setting The display when the main power is turned on When F4 to F9 are displayed continue to press the SELECT button until F3 is displayed Press the SELECT button until 11 is displayed Press the ENTE...

Page 16: ...uation procedure 1 Remove the blank caps of the gas pipe and liquid pipe and check that the valves are closed 2 Remove the charging port cap 3 Connect a vacuum pump and a pressure gauge to a charging hose and connect it to the charging port 4 Activate the vacuum pump and vacuum the indoor unit and connection piping until the pressure gauge becomes 100 7 kPa 755mm Hg Evacuate from both the gas pipe...

Page 17: ... has condensed in the 3 way valve of the outdoor unit could travel to the indoor unit Therefore use putty in the space between the pipe and the insulation to prevent the entry of water to the indoor units Fig A Putty Insulation 9 TEST RUN 9 1 Indoor unit connection check Normal operation will not be possible without performing the Indoor unit connection check 9 1 1 Things to confirm before startin...

Page 18: ...he EN TER button for more than 3 seconds 2 When errors other than the address of the overlap indoor unit exist press SE LECT button to switch to the next error If error occurs it will display Ad address number 9 2 Test run Before the test operation check the following items 1 Is there a gas leakage At pipe connections flange connections and brazed areas 2 Is the system charged with the specified v...

Page 19: ...r E 8 3 2 Outdoor unit liquid pipe temp thermistor 2 error E 8 4 1 Outdoor unit current sensor 1 error permanent stop E 8 6 1 Outdoor unit discharge pressure sensor error E 8 6 3 Outdoor unit suction pressure sensor error E 8 6 4 Outdoor unit high pressure switch 1 error Outdoor unit actuator error E 9 3 1 Outdoor unit inverter compressor start up error E 9 4 1 Outdoor unit trip detection E 9 5 5 ...

Reviews: