En-13

73

Electricity meter 
pulse setting 2 *3

Setting number (00xx)

7

3

0

0

Setting number (01xx)

0

1

······

···

···

Setting number (98xx)

9

8

Setting number (99xx)

9

9

Set the hundreds digit and thousands digit of the electricity meter pulse setting connected 
to CN135.

90

(Forbidden)

9

0

0

0

(Factory default)

*1: Do not set this for outdoor units with Slave setting.
*2:  When electricity meter No. is set to “000” and “201 to 299”, the pulses input to CN135 

become ineffective. Available setting number is "001" to "200"

*3:  When the electricity meter pulse setting is set to “0000”, the pulses input to CN135 

become ineffective. Available setting number is "0001" to "9999"

(1)  Turn on the power of the outdoor unit and enter standby mode.

•  When system is normal 

POWER/MODE lamp lights up. (ERROR 
lamp is off.)

•  When system is abnormal 

Check the settings as there is an error in 
the settings for outdoor unit address 
(DIP switch SET 3-1, 2) or number of 
connected slave units (DIP switch SET 
3-3, 4).

POWER/MODE 

lamp: ON

ERROR 

lamp: OFF

SELECT button

ENTER 

button

MODE/EXIT 

button

POWER

LED105

LED104

ERROR

MODE

LED101

(GREEN)

MODE

/EXIT

SELECT

ENTER

SW107

SW108

SW109

LED102

(RED)

7 segment 

display:  

turn off

POWER/MODE 

lamp: ON

7 segment 

display: “-” 

display

ERROR lamp: 

Blinking

POWER

LED105

LED104

ERROR

MODE

LED101

(GREEN)

MODE

/EXIT

SELECT

ENTER

SW107

SW108

SW109

LED102

(RED)

(2) Setting 

method

Use the “MODE/EXIT”, “SELECT”, and “ENTER” buttons to con

fi

 gure settings according 

to the procedures below.
(If no setting is made, the factory default setting will be displayed.)

: Press the “MODE/EXIT” button

: Press the “SELECT” button

: Press the “ENTER” button.

: Press the “ENTER” button for more than 3 seconds.

1: Function setting

7 segment LED display 
(LED 105, LED 104)

(Flashing)

First 2 digits Last 2 digits

(When [F3] to [F9] are displayed, continue to press the 
“SELECT” button until [F2] is displayed.)

2: Setting the 

fi

 rst 

2 digits

3: Setting the last 2 digits

Continue to press the “SELECT” button until the 
desired number appears at the last 2 digits.

Every press of the 
“SELECT” button will 
change the setting 
number for the 

fi

 rst 2 

digits.

(Continue to press the “SELECT” 
button until the desired number 
appears at the last 2 digits.)

Setting is complete when the lamp lights up

Press “ENTER” button to return to “2. Setting the 

fi

 rst 2 digits” (If there is no operation for 5 seconds 

after the setting, the display will return to “2: Setting 
the 

fi

 rst 2 digits”.)

Setting is complete when the lamp lights up

Press “ENTER” button to return to “2. Setting the 

fi

 rst 2 digits” (If there is no operation for 5 seconds 

after the setting, the display will return to “2: Setting 
the 

fi

 rst 2 digits”.)

EXIT: Press the “MODE/EXIT” button to cancel the setting mode.

7.5.  Address setting for signal ampli

fi

 ers

7.5.1  Address setting for signal ampli

fi

 ers

When using signal ampli

fi

 ers, the address for signal ampli

fi

 ers must be set.

The address for signal ampli

fi

 ers can be set automatically from 1 outdoor unit (master 

unit) on the network.
Refer to “Fig. Wiring example for automatic address setting” (7.6.1 chapter) for the wiring 
example.
(For manual setting of address, refer to the signal ampli

fi

 er installation manual.)

7.5.2  Automatic address setting for signal ampli

fi

 ers

When setting the address of the signal ampli

fi

 er, please use the factory setting. (See the 

installation manual of the signal ampli

fi

 er)

•  When the system is normal, nothing will be displayed on the 7 segment display.
•  When ERROR is displayed, inspect the units. 
Use the “MODE/EXIT”, “SELECT”, and “ENTER” buttons on the outdoor unit PC board to 
con

fi

 gure settings according to the procedures below.

9380545170_IM.indb   13

9380545170_IM.indb   13

5/19/2016   2:23:17 PM

5/19/2016   2:23:17 PM

Summary of Contents for AJH040LBLAH

Page 1: ... DIŞ ÜNİTE For authorized service personnel only Nur für autorisiertes Fachpersonal Uniquement réservé aux techniciens agréés Sólo para personal de servicio autorizado A uso esclusivo del personale tecnico autorizzato Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό Apenas para técnicos de assistência autorizados Только для авторизованного обслуживающего персонала Yalnızca yetkili servis personeli için ...

Page 2: ...c shock or fire Securely install the electrical box cover on the unit An improperly installed electrical box cover can cause serious accidents such as electric shock or fire through exposure to dust or water Do not turn ON the power until all work has been completed Turning ON the power before the work is completed can cause serious accidents such as electric shock or fire After the installation m...

Page 3: ...n or water leakage When setting it up near the equipment that generates electromagnetic waves and the equipment that generates the higher harmonics wave be sure to take measures against noise Otherwise it may cause malfunction or failure When energizing to the crankcase heater please turn on the power 12 hours or earlier before operation begins When the energizing time is short it may cause failur...

Page 4: ...e installed more than 1 meter apart you could still receive noise under some signal conditions Keep the length of the piping of the indoor and outdoor units within the allowable range For maintenance purposes do not bury the piping 3 2 Drain processing CAUTION Perform drain work in accordance with this Manual and ensure that the drain water is properly drained If the drain work is not carried out ...

Page 5: ...of the unit Otherwise the suction grilles on the sides of the unit may be deformed Front view Rear view Fig B Handle Handle Suction grille Fig A 3 5 Installing the unit Please install the outdoor unit without slant within 3 degrees Install 4 anchor bolts at the locations indicated with arrows in the figure To reduce vibration do not install the unit directly on the ground Install it on a secure ba...

Page 6: ...n method Outdoor 1 month or more Pinch pipes Less than 1 month Pinch or tape pipes Indoor Pinch or tape pipes Protect the pipes to prevent the entry of moisture and dust Especially pay attention when passing the pipes through a hole or connecting the end of a pipe to the outdoor unit 4 SYSTEM CONFIGURATION 4 1 System configuration CAUTION Always keep to the limit on the total amount of refrigerant...

Page 7: ...ontal line View D View C Horizontal line Vertical line Gas pipe Liquid pipe Outdoor unit side Outdoor unit side H1 0 to 10 mm H2 0 to 10 mm α1 0 to 1 β1 10 to 10 α2 0 to 1 β2 10 to 10 PROHIBITED CAUTION Do not connect a separation tube after a header Leave the distance 0 5 m or more for straight part to branch tube and header Main pipe 0 5 m or more To indoor unit To indoor unit To indoor unit Mai...

Page 8: ...ve any burrs 3 Insert the flare nut always use the flare nut attached to the indoor and outdoor units respectively onto the pipe and perform the flare processing with a flare tool Leakage of refrigerant may result if other flare nuts are used 4 Protect the pipes by pinching them or with tape to prevent dust dirt or water from entering the pipes L Check if L is flared uniformly and is not cracked o...

Page 9: ...breaker is too high the amperage at which the breaker cuts out may decrease Use a breaker Included with earth leakage circuit breaker that is capable of handling high frequencies Because the outdoor unit is inverter controlled a high frequency earth leakage circuit breaker is necessary to prevent a malfunction of the breaker itself When the electrical switchboard is installed outdoors place it und...

Page 10: ...g 2 NOTE Do not use loop wiring This may lead to parts damage and erroneous operation Outdoor unit Indoor unit Signal Amplifier System Controller Touch Panel Controller Transmission line Terminal resistor Terminal resistor NS 1 NS 2 F H L G K J E 6 4 3 Enabling Disabling automatic address setting You can enable disable automatic address setting for the indoor unit and the signal ampli fier To enab...

Page 11: ...rminal Sleeve Screw with special washer Ring terminal Cable Shielding the transmission cable Connect both ends of the shielded wire of the transmission cable to the earth ground terminal of the equipment or to the earth ground screw near the terminal Be sure to use one side of a twisted pair cable when using transmission cable with 2 sets of twisted pair cables Wind with insulation tape to prevent...

Page 12: ... This is the output signal for base heater Output signal ON when the outdoor temperature goes down below 2 C and signal OFF at the outdoor temperature 4 C Voltage power supply input voltage cable 0 82 mm2 18AWG P C B Base heater 9 CN115 Black 8 8 Connect to pin 1 and pin 3 No connection pin 2 and pin 4 9 The allowable current is 1 A or less 7 FIELD SETTING CAUTION Discharge the static electricity ...

Page 13: ...efrigerant circuit address Rotary Switch Setting Setting Setting range Type of switch REF AD 10 1 Refrigerant circuit address 0 99 Setting example 63 0 0 0 1 0 1 2 0 2 REF AD 10 REF AD 1 Rotary Switch REF AD 1 Factory setting 0 Rotary Switch REF AD 10 Factory setting 0 98 9 8 99 9 9 7 4 Push button setting Various functions can be set Set when necessary Perform settings after all indoor units have...

Page 14: ...s Last 2 digits When F3 to F9 are displayed continue to press the SELECT button until F2 is displayed 2 Setting the first 2 digits 3 Setting the last 2 digits Continue to press the SELECT button until the desired number appears at the last 2 digits Every press of the SELECT button will change the setting number for the first 2 digits Continue to press the SELECT button until the desired number app...

Page 15: ...e 7 segment display When ERROR is displayed inspect the units Use the MODE EXIT SELECT and ENTER buttons on the outdoor unit PC board to configure settings according to the procedures below 1 Function setting The display when the main power is turned on When F4 to F9 are displayed continue to press the SELECT button until F3 is displayed Press the SELECT button until 11 is displayed Press the ENTE...

Page 16: ...uation procedure 1 Remove the blank caps of the gas pipe and liquid pipe and check that the valves are closed 2 Remove the charging port cap 3 Connect a vacuum pump and a pressure gauge to a charging hose and connect it to the charging port 4 Activate the vacuum pump and vacuum the indoor unit and connection piping until the pressure gauge becomes 100 7 kPa 755mm Hg Evacuate from both the gas pipe...

Page 17: ... has condensed in the 3 way valve of the outdoor unit could travel to the indoor unit Therefore use putty in the space between the pipe and the insulation to prevent the entry of water to the indoor units Fig A Putty Insulation 9 TEST RUN 9 1 Indoor unit connection check Normal operation will not be possible without performing the Indoor unit connection check 9 1 1 Things to confirm before startin...

Page 18: ...he EN TER button for more than 3 seconds 2 When errors other than the address of the overlap indoor unit exist press SE LECT button to switch to the next error If error occurs it will display Ad address number 9 2 Test run Before the test operation check the following items 1 Is there a gas leakage At pipe connections flange connections and brazed areas 2 Is the system charged with the specified v...

Page 19: ...r E 8 3 2 Outdoor unit liquid pipe temp thermistor 2 error E 8 4 1 Outdoor unit current sensor 1 error permanent stop E 8 6 1 Outdoor unit discharge pressure sensor error E 8 6 3 Outdoor unit suction pressure sensor error E 8 6 4 Outdoor unit high pressure switch 1 error Outdoor unit actuator error E 9 3 1 Outdoor unit inverter compressor start up error E 9 4 1 Outdoor unit trip detection E 9 5 5 ...

Reviews: