background image

En-7

CAUTION

Hold the torque wrench at its grip, keeping it in a right angle with the pipe, in order to 
tighten the 

fl

 are nut correctly.

Outer panel may be distorted if 
fastened only with a wrench. Be 
sure to 

fi

 x the elementary part with a 

holding wrench (spanner) and fasten 
with a torque wrench (refer to below 
diagram). Do not apply force to the 
blank cap of the valve or hang a 
wrench, etc., on the cap. If blank cap 
is broken, it may cause leakage of 
refrigerant.

Blank cap

Flare nut

90°

Torque wrench

Holding 
wrench

Torque 
wrench

Flare nut [mm (in)]

Tightening torque [N·m (kgf·cm)]

6.35 (1/4) dia.

16 to 18 (160 to 180)

9.52 (3/8) dia.

32 to 42 (320 to 420)

12.70 (1/2) dia.

49 to 61 (490 to 610)

15.88 (5/8) dia.

63 to 75 (630 to 750)

19.05 (3/4) dia.

90 to 110 (900 to 1100)

In the case of AJ*054LBLAH

It is necessary to change a connection 
pipe diameter by using Reducer.
(1)  Reducer must be brazed in the 

outside of the outdoor unit.

(2) Distance 

between 

3-way 

valve 

and 

reducer 

 1 m

(3)  The part of Reducer do insulation 

processing after brazing.

Example: Case of front connection

Connection pipe (Gas) 
(Pipe outside dia.: 
19.05 mm (3/4 in)

Brazing

1 m or less

Reducer 
(accessory)

Connection pipe (Gas) 
(Pipe outside dia.: 
15.88 mm (5/8 in))

5.4.4  Handling precautions for the valves

•  Mounted part of Blank cap is sealed for protection.
•  Fasten blank cap tightly after opening valves.

Operating the valves

•  Use a hexagon wrench (size 4 mm).

Opening:

(1)  Insert the hexagon wrench into the 

valve shaft, and turn it counterclock-
wise.

(2) Stop 

turning 

when the valve shaft can 

no longer be turned. (Open position)

Closing:

(1)  Insert the hexagon wrench into the 

valve shaft, and turn it clockwise.

(2) Stop 

turning 

when the valve shaft can 

no longer be turned. (Closed position)

Opening 
direction

Hexagon wrench

Seal 

(blank cap 
installation 
portion)

Liquid 
pipe

Gas pipe

Opening 
direction

5.4. Pipe 

connection

CAUTION

Do not use mineral oil on a 

fl

 ared part. Prevent mineral oil from getting into the system 

as this would reduce the lifetime of the units.

While brazing the pipes, be sure to blow dry nitrogen gas through them.

The maximum lengths of this product are shown in the table. If the units are further apart 
than this, correct operation cannot be guaranteed.

5.4.1 Flaring

Use special pipe cutter and 

fl

 are tool exclusive for R410A.

(1)  Cut the connection pipe to the necessary length with a pipe cutter.
(2)  Hold the pipe downward so that the cuttings will not enter the pipe and remove any 

burrs.

(3) Insert 

the 

fl

 are nut (always use the 

fl

 are nut attached to the indoor and outdoor units 

respectively) onto the pipe and perform the 

fl

 are processing with a 

fl

 are tool. Leakage 

of refrigerant may result if other 

fl

 are nuts are used.

(4)  Protect the pipes by pinching them or with tape to prevent dust, dirt, or water from 

entering the pipes.

L

Check if [L] is 

fl

 ared uniformly 

and is not cracked or scratched.

Pipe

A

B

Die

Pipe outside diameter 

[mm (in)]

Dimension A [mm]

Dimension B

0

-0.4

 

[mm]

Flare tool for R410A, 

clutch type

6.35 (1/4)

0 to 0.5

9.1

9.52 (3/8)

13.2

12.70 (1/2)

16.6

15.88 (5/8)

19.7

19.05 (3/4)

24.0

When using conventional (R22) 

fl

 are tools to 

fl

 are R410A pipes, the dimension A should 

be approximately 0.5 mm more than indicated in the table (for 

fl

 aring with R410A 

fl

 are 

tools) to achieve the speci

fi

 ed 

fl

 aring. Use a thickness gauge to measure the dimension A. 

It is recommended that a R410A 

fl

 aring tool is used.

Width across 

fl

 ats

Pipe outside diameter 

[mm (in)]

Width across flats of 

Flare nut [mm]

6.35 (1/4)

17

9.52 (3/8)

22

12.70 (1/2)

26

15.88 (5/8)

29

19.05 (3/4)

36

5.4.2 Bending pipes

CAUTION

To prevent breaking of the pipe, avoid sharp bends. Bend the pipe with a radius of 
curvature of 100 mm or more.

If the pipe is bent repeatedly at the same place, it will break.

•  If pipes are shaped by hand, be careful not to collapse them.
•  Do not bend the pipes at an angle of more than 90°.
•  When pipes are repeatedly bent or stretched, the material will harden, making it dif

fi

 cult 

to bend or stretch them any more.

•  Do not bend or stretch the pipes more than 3 times.

5.4.3 Pipe connection

CAUTION

Be sure to install the pipe against the port on the indoor unit and the outdoor unit cor-
rectly. If the centering is improper, the 

fl

 are nut cannot be tightened smoothly. 

If the 

fl

 are nut is forced to turn, the threads will be damaged.

Do not remove the 

fl

 are nut from the outdoor unit pipe until immediately before connect-

ing the connection pipe.

After installing the piping, make sure that the connection pipes do not touch the com-
pressor or outer panel. If the pipes touch the compressor or outer panel, they will vibrate 
and produce noise.

(1)  Detach the caps and plugs from the 

pipes.

(2)  Center the pipe against the port on the 

outdoor unit, and then turn the 

fl

 are nut 

by hand.

(3) Tighten 

the 

fl

 are nut of the connection 

pipe at the outdoor unit valve connec-
tor.

(4)  After tightening the 

fl

 are nut by hand, 

use a torque wrench to fully tighten it.

3-way valve (Liquid)

3-way valve 
(Gas)

Connection pipe 
(Liquid)

Flare nut

Connection 
pipe (Gas)

Flare nut

9380545170_IM.indb   7

9380545170_IM.indb   7

5/19/2016   2:23:16 PM

5/19/2016   2:23:16 PM

Summary of Contents for AJH040LBLAH

Page 1: ... DIŞ ÜNİTE For authorized service personnel only Nur für autorisiertes Fachpersonal Uniquement réservé aux techniciens agréés Sólo para personal de servicio autorizado A uso esclusivo del personale tecnico autorizzato Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό Apenas para técnicos de assistência autorizados Только для авторизованного обслуживающего персонала Yalnızca yetkili servis personeli için ...

Page 2: ...c shock or fire Securely install the electrical box cover on the unit An improperly installed electrical box cover can cause serious accidents such as electric shock or fire through exposure to dust or water Do not turn ON the power until all work has been completed Turning ON the power before the work is completed can cause serious accidents such as electric shock or fire After the installation m...

Page 3: ...n or water leakage When setting it up near the equipment that generates electromagnetic waves and the equipment that generates the higher harmonics wave be sure to take measures against noise Otherwise it may cause malfunction or failure When energizing to the crankcase heater please turn on the power 12 hours or earlier before operation begins When the energizing time is short it may cause failur...

Page 4: ...e installed more than 1 meter apart you could still receive noise under some signal conditions Keep the length of the piping of the indoor and outdoor units within the allowable range For maintenance purposes do not bury the piping 3 2 Drain processing CAUTION Perform drain work in accordance with this Manual and ensure that the drain water is properly drained If the drain work is not carried out ...

Page 5: ...of the unit Otherwise the suction grilles on the sides of the unit may be deformed Front view Rear view Fig B Handle Handle Suction grille Fig A 3 5 Installing the unit Please install the outdoor unit without slant within 3 degrees Install 4 anchor bolts at the locations indicated with arrows in the figure To reduce vibration do not install the unit directly on the ground Install it on a secure ba...

Page 6: ...n method Outdoor 1 month or more Pinch pipes Less than 1 month Pinch or tape pipes Indoor Pinch or tape pipes Protect the pipes to prevent the entry of moisture and dust Especially pay attention when passing the pipes through a hole or connecting the end of a pipe to the outdoor unit 4 SYSTEM CONFIGURATION 4 1 System configuration CAUTION Always keep to the limit on the total amount of refrigerant...

Page 7: ...ontal line View D View C Horizontal line Vertical line Gas pipe Liquid pipe Outdoor unit side Outdoor unit side H1 0 to 10 mm H2 0 to 10 mm α1 0 to 1 β1 10 to 10 α2 0 to 1 β2 10 to 10 PROHIBITED CAUTION Do not connect a separation tube after a header Leave the distance 0 5 m or more for straight part to branch tube and header Main pipe 0 5 m or more To indoor unit To indoor unit To indoor unit Mai...

Page 8: ...ve any burrs 3 Insert the flare nut always use the flare nut attached to the indoor and outdoor units respectively onto the pipe and perform the flare processing with a flare tool Leakage of refrigerant may result if other flare nuts are used 4 Protect the pipes by pinching them or with tape to prevent dust dirt or water from entering the pipes L Check if L is flared uniformly and is not cracked o...

Page 9: ...breaker is too high the amperage at which the breaker cuts out may decrease Use a breaker Included with earth leakage circuit breaker that is capable of handling high frequencies Because the outdoor unit is inverter controlled a high frequency earth leakage circuit breaker is necessary to prevent a malfunction of the breaker itself When the electrical switchboard is installed outdoors place it und...

Page 10: ...g 2 NOTE Do not use loop wiring This may lead to parts damage and erroneous operation Outdoor unit Indoor unit Signal Amplifier System Controller Touch Panel Controller Transmission line Terminal resistor Terminal resistor NS 1 NS 2 F H L G K J E 6 4 3 Enabling Disabling automatic address setting You can enable disable automatic address setting for the indoor unit and the signal ampli fier To enab...

Page 11: ...rminal Sleeve Screw with special washer Ring terminal Cable Shielding the transmission cable Connect both ends of the shielded wire of the transmission cable to the earth ground terminal of the equipment or to the earth ground screw near the terminal Be sure to use one side of a twisted pair cable when using transmission cable with 2 sets of twisted pair cables Wind with insulation tape to prevent...

Page 12: ... This is the output signal for base heater Output signal ON when the outdoor temperature goes down below 2 C and signal OFF at the outdoor temperature 4 C Voltage power supply input voltage cable 0 82 mm2 18AWG P C B Base heater 9 CN115 Black 8 8 Connect to pin 1 and pin 3 No connection pin 2 and pin 4 9 The allowable current is 1 A or less 7 FIELD SETTING CAUTION Discharge the static electricity ...

Page 13: ...efrigerant circuit address Rotary Switch Setting Setting Setting range Type of switch REF AD 10 1 Refrigerant circuit address 0 99 Setting example 63 0 0 0 1 0 1 2 0 2 REF AD 10 REF AD 1 Rotary Switch REF AD 1 Factory setting 0 Rotary Switch REF AD 10 Factory setting 0 98 9 8 99 9 9 7 4 Push button setting Various functions can be set Set when necessary Perform settings after all indoor units have...

Page 14: ...s Last 2 digits When F3 to F9 are displayed continue to press the SELECT button until F2 is displayed 2 Setting the first 2 digits 3 Setting the last 2 digits Continue to press the SELECT button until the desired number appears at the last 2 digits Every press of the SELECT button will change the setting number for the first 2 digits Continue to press the SELECT button until the desired number app...

Page 15: ...e 7 segment display When ERROR is displayed inspect the units Use the MODE EXIT SELECT and ENTER buttons on the outdoor unit PC board to configure settings according to the procedures below 1 Function setting The display when the main power is turned on When F4 to F9 are displayed continue to press the SELECT button until F3 is displayed Press the SELECT button until 11 is displayed Press the ENTE...

Page 16: ...uation procedure 1 Remove the blank caps of the gas pipe and liquid pipe and check that the valves are closed 2 Remove the charging port cap 3 Connect a vacuum pump and a pressure gauge to a charging hose and connect it to the charging port 4 Activate the vacuum pump and vacuum the indoor unit and connection piping until the pressure gauge becomes 100 7 kPa 755mm Hg Evacuate from both the gas pipe...

Page 17: ... has condensed in the 3 way valve of the outdoor unit could travel to the indoor unit Therefore use putty in the space between the pipe and the insulation to prevent the entry of water to the indoor units Fig A Putty Insulation 9 TEST RUN 9 1 Indoor unit connection check Normal operation will not be possible without performing the Indoor unit connection check 9 1 1 Things to confirm before startin...

Page 18: ...he EN TER button for more than 3 seconds 2 When errors other than the address of the overlap indoor unit exist press SE LECT button to switch to the next error If error occurs it will display Ad address number 9 2 Test run Before the test operation check the following items 1 Is there a gas leakage At pipe connections flange connections and brazed areas 2 Is the system charged with the specified v...

Page 19: ...r E 8 3 2 Outdoor unit liquid pipe temp thermistor 2 error E 8 4 1 Outdoor unit current sensor 1 error permanent stop E 8 6 1 Outdoor unit discharge pressure sensor error E 8 6 3 Outdoor unit suction pressure sensor error E 8 6 4 Outdoor unit high pressure switch 1 error Outdoor unit actuator error E 9 3 1 Outdoor unit inverter compressor start up error E 9 4 1 Outdoor unit trip detection E 9 5 5 ...

Reviews: