background image

En-5

Table. B  (Diameter of piping used between outdoor unit and 

fi

 rst separation 

tubes or headers)

MODEL

Outdoor 

unit cool-

ing capac-

ity [kW]

Diameter of piping [mm (in.)]

Between outdoor unit 

and the farthest indoor 

unit < 90m *3

Between outdoor unit 

and the farthest indoor 

unit 

 90m *3

Liquid pipe

Gas pipe

Liquid pipe

Gas pipe

AJ*040LBLAH

12.1

9.52 (3/8)

15.88 (5/8)

9.52 (3/8)

19.05 (3/4)

AJ*045LBLAH

14.0

9.52 (3/8)

15.88 (5/8)

9.52 (3/8)

19.05 (3/4)

AJ*054LBLAH

15.5

9.52 (3/8)

19.05 (3/4)

9.52 (3/8)

19.05 (3/4)

*3: Pipe Length: “a + f” or “a + p” of “4.1. SYSTEM CONFIGURATION”

Table. C   (Diameter  of  piping  used  between  separation  tubes)

Total cooling 

capacity of indoor 

unit [kW]

Outside diameter [mm(in.)]

Separation 

tube *4

Header *4

Liquid pipe

Gas pipe

4.4 to 11.1

9.52 (3/8)

15.88 (5/8)

UTP-AX054A

UTR-H0906L
UTR-H0908L

11.2 to 20.1

9.52 (3/8)

19.05 (3/4)

*4:  For the installation method, please refer to the installation manuals for indoor unit, 

separation tubes or headers.

If pipe diameter Table C > Table B , select pipe size from Table B.
“Total cooling capacity of indoor unit” is the total value for the cooling capacity of indoor 
unit connected downstream.
Use a standard separation tube for pipe branching. Do not use a T tube as it does not 
separate the refrigerant evenly.

Table. D   (Diameter  of  piping  used  between separation tube and indoor unit)

Model code of 

indoor unit 

Outside diameter [mm(in.)]

Liquid pipe

Gas pipe

07 to 14

6.35 (1/4)

12.70 (1/2)

18 to 30

9.52 (3/8)

15.88 (5/8)

36 to 54  *5

9.52 (3/8)

19.05 (3/4)

*5: If pipe diameter Table D > Table C , using of pipe size from Table C is preferable.

(Use reducer to change the diameter of connection pipe.)

Table. E  (Indoor unit capacity comparison table - The indication of power is 

different depending on the model.)

Model code of 

indoor unit

04

07

09

12

14

18

24

30

36

45

54

Capacity [kW]

1.1

2.2

2.8

3.6

4.5

5.6

7.1

9.0

11.2 12.5 14.0

In the case of ARXB07LALH:  equivalent to model code of indoor unit

 Model code 07 

 Capacity=2.2kW

4.3.  Protection of pipes

Location

Working period

Protection method

Outdoor

1 month or more

Pinch pipes

Less than 1 month

Pinch or tape pipes

Indoor

Pinch or tape pipes

•  Protect the pipes to prevent the entry of moisture and dust.
•  Especially pay attention when passing the pipes through a hole or connecting the end of 

a pipe to the outdoor unit.

4. SYSTEM 

CONFIGURATION

4.1. System 

con

fi

 guration

CAUTION

Always keep to the limit on the total amount of refrigerant. Exceeding the limit on the 
total amount of refrigerant when charging will lead to malfunction.

•  Between outdoor unit and the farthest indoor unit

a + f 

 120 m, a + p 

 120 m

• Between the 

fi

 rst separation tube and the farthest indoor unit

 40 m, p 

 40 m

•  Between the nearest indoor unit and the outdoor unit

a + b + h 

 5 m, a+c+q 

 5 m

•  Between outdoor unit and the 

fi

 rst separation tube

 3 m

•  Difference in height between outdoor units and indoor  units (H1*)

50 m or less: Outdoor unit is higher than indoor unit
40 m or less: Outdoor unit is lower than indoor unit

•  Difference in height between indoor units and indoor units

H2 

 15 m, H3 

 15 m

•  Maximum total equivalent pipe length

a + f + h + j + l + n + p + q + s + u 

 180 m

•  Total refrigerant amount 

 15.7 kg

Fig. A 

Outdoor 

unit 

Indoor 

unit

Indoor 

unit

Indoor 

unit

Indoor 

unit

Indoor 

unit

Indoor 

unit

Indoor 

unit

Indoor 

unit

Indoor 

unit

H1*

H2

H3

f

h

p

q

j

s

u

l

n

b

c

a

4.2. Pipe 

selection

CAUTION

This unit is designed speci

fi

 cally for use with the R410A refrigerant.

Pipes for R407C or R22 may not be used with this unit.

Do not use existing pipes.

Improper pipe selection will degrade performance.

First separation 

tube (optional)

Separation tube 

(optional)

Pipe size 

(table B)

Pipe size 

(table C)

Pipe size 

(table D)

Indoor 

unit

Indoor 

unit

Indoor 

unit

Indoor 

unit

Indoor 

unit

Indoor 

unit

Table. A  (Wall  thickness  and  pipe  material  for  each  diameter)

Outside Diameter

mm 

(in)

6.35 

(1/4)

9.52 

(3/8)

12.70 

(1/2)

15.88 

(5/8)

19.05 

(3/4)

Wall Thickness*2

mm 

(in)

0.8 

(0.032)

0.8 

(0.032)

0.8 

(0.032)

1.0 

(0.039)

1.2 

(0.047)

Material

COPPER*1

  

JIS H3300 C1220T-O or equivalent

Please select the pipe size in accordance with local rules.
*1: Allowable tensile stress 

 33 N/mm

*2:  Endurance pressure of the pipes 4.2 MPa

9380545170_IM.indb   5

9380545170_IM.indb   5

5/19/2016   2:23:16 PM

5/19/2016   2:23:16 PM

Summary of Contents for AJH040LBLAH

Page 1: ... DIŞ ÜNİTE For authorized service personnel only Nur für autorisiertes Fachpersonal Uniquement réservé aux techniciens agréés Sólo para personal de servicio autorizado A uso esclusivo del personale tecnico autorizzato Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό Apenas para técnicos de assistência autorizados Только для авторизованного обслуживающего персонала Yalnızca yetkili servis personeli için ...

Page 2: ...c shock or fire Securely install the electrical box cover on the unit An improperly installed electrical box cover can cause serious accidents such as electric shock or fire through exposure to dust or water Do not turn ON the power until all work has been completed Turning ON the power before the work is completed can cause serious accidents such as electric shock or fire After the installation m...

Page 3: ...n or water leakage When setting it up near the equipment that generates electromagnetic waves and the equipment that generates the higher harmonics wave be sure to take measures against noise Otherwise it may cause malfunction or failure When energizing to the crankcase heater please turn on the power 12 hours or earlier before operation begins When the energizing time is short it may cause failur...

Page 4: ...e installed more than 1 meter apart you could still receive noise under some signal conditions Keep the length of the piping of the indoor and outdoor units within the allowable range For maintenance purposes do not bury the piping 3 2 Drain processing CAUTION Perform drain work in accordance with this Manual and ensure that the drain water is properly drained If the drain work is not carried out ...

Page 5: ...of the unit Otherwise the suction grilles on the sides of the unit may be deformed Front view Rear view Fig B Handle Handle Suction grille Fig A 3 5 Installing the unit Please install the outdoor unit without slant within 3 degrees Install 4 anchor bolts at the locations indicated with arrows in the figure To reduce vibration do not install the unit directly on the ground Install it on a secure ba...

Page 6: ...n method Outdoor 1 month or more Pinch pipes Less than 1 month Pinch or tape pipes Indoor Pinch or tape pipes Protect the pipes to prevent the entry of moisture and dust Especially pay attention when passing the pipes through a hole or connecting the end of a pipe to the outdoor unit 4 SYSTEM CONFIGURATION 4 1 System configuration CAUTION Always keep to the limit on the total amount of refrigerant...

Page 7: ...ontal line View D View C Horizontal line Vertical line Gas pipe Liquid pipe Outdoor unit side Outdoor unit side H1 0 to 10 mm H2 0 to 10 mm α1 0 to 1 β1 10 to 10 α2 0 to 1 β2 10 to 10 PROHIBITED CAUTION Do not connect a separation tube after a header Leave the distance 0 5 m or more for straight part to branch tube and header Main pipe 0 5 m or more To indoor unit To indoor unit To indoor unit Mai...

Page 8: ...ve any burrs 3 Insert the flare nut always use the flare nut attached to the indoor and outdoor units respectively onto the pipe and perform the flare processing with a flare tool Leakage of refrigerant may result if other flare nuts are used 4 Protect the pipes by pinching them or with tape to prevent dust dirt or water from entering the pipes L Check if L is flared uniformly and is not cracked o...

Page 9: ...breaker is too high the amperage at which the breaker cuts out may decrease Use a breaker Included with earth leakage circuit breaker that is capable of handling high frequencies Because the outdoor unit is inverter controlled a high frequency earth leakage circuit breaker is necessary to prevent a malfunction of the breaker itself When the electrical switchboard is installed outdoors place it und...

Page 10: ...g 2 NOTE Do not use loop wiring This may lead to parts damage and erroneous operation Outdoor unit Indoor unit Signal Amplifier System Controller Touch Panel Controller Transmission line Terminal resistor Terminal resistor NS 1 NS 2 F H L G K J E 6 4 3 Enabling Disabling automatic address setting You can enable disable automatic address setting for the indoor unit and the signal ampli fier To enab...

Page 11: ...rminal Sleeve Screw with special washer Ring terminal Cable Shielding the transmission cable Connect both ends of the shielded wire of the transmission cable to the earth ground terminal of the equipment or to the earth ground screw near the terminal Be sure to use one side of a twisted pair cable when using transmission cable with 2 sets of twisted pair cables Wind with insulation tape to prevent...

Page 12: ... This is the output signal for base heater Output signal ON when the outdoor temperature goes down below 2 C and signal OFF at the outdoor temperature 4 C Voltage power supply input voltage cable 0 82 mm2 18AWG P C B Base heater 9 CN115 Black 8 8 Connect to pin 1 and pin 3 No connection pin 2 and pin 4 9 The allowable current is 1 A or less 7 FIELD SETTING CAUTION Discharge the static electricity ...

Page 13: ...efrigerant circuit address Rotary Switch Setting Setting Setting range Type of switch REF AD 10 1 Refrigerant circuit address 0 99 Setting example 63 0 0 0 1 0 1 2 0 2 REF AD 10 REF AD 1 Rotary Switch REF AD 1 Factory setting 0 Rotary Switch REF AD 10 Factory setting 0 98 9 8 99 9 9 7 4 Push button setting Various functions can be set Set when necessary Perform settings after all indoor units have...

Page 14: ...s Last 2 digits When F3 to F9 are displayed continue to press the SELECT button until F2 is displayed 2 Setting the first 2 digits 3 Setting the last 2 digits Continue to press the SELECT button until the desired number appears at the last 2 digits Every press of the SELECT button will change the setting number for the first 2 digits Continue to press the SELECT button until the desired number app...

Page 15: ...e 7 segment display When ERROR is displayed inspect the units Use the MODE EXIT SELECT and ENTER buttons on the outdoor unit PC board to configure settings according to the procedures below 1 Function setting The display when the main power is turned on When F4 to F9 are displayed continue to press the SELECT button until F3 is displayed Press the SELECT button until 11 is displayed Press the ENTE...

Page 16: ...uation procedure 1 Remove the blank caps of the gas pipe and liquid pipe and check that the valves are closed 2 Remove the charging port cap 3 Connect a vacuum pump and a pressure gauge to a charging hose and connect it to the charging port 4 Activate the vacuum pump and vacuum the indoor unit and connection piping until the pressure gauge becomes 100 7 kPa 755mm Hg Evacuate from both the gas pipe...

Page 17: ... has condensed in the 3 way valve of the outdoor unit could travel to the indoor unit Therefore use putty in the space between the pipe and the insulation to prevent the entry of water to the indoor units Fig A Putty Insulation 9 TEST RUN 9 1 Indoor unit connection check Normal operation will not be possible without performing the Indoor unit connection check 9 1 1 Things to confirm before startin...

Page 18: ...he EN TER button for more than 3 seconds 2 When errors other than the address of the overlap indoor unit exist press SE LECT button to switch to the next error If error occurs it will display Ad address number 9 2 Test run Before the test operation check the following items 1 Is there a gas leakage At pipe connections flange connections and brazed areas 2 Is the system charged with the specified v...

Page 19: ...r E 8 3 2 Outdoor unit liquid pipe temp thermistor 2 error E 8 4 1 Outdoor unit current sensor 1 error permanent stop E 8 6 1 Outdoor unit discharge pressure sensor error E 8 6 3 Outdoor unit suction pressure sensor error E 8 6 4 Outdoor unit high pressure switch 1 error Outdoor unit actuator error E 9 3 1 Outdoor unit inverter compressor start up error E 9 4 1 Outdoor unit trip detection E 9 5 5 ...

Reviews: