Page 40
H
Possible defective panel. Consult factory for technical support
J
Download manual or refer to zone panel inside cover for DIP switch
setting
K
Verify voltage input to panel. Voltage input must be between 21 and 29
VAC
2 zone panel troubleshooting steps
Step
Action
Check(s)
1
Turn off power to zone panel and remove cover.
2
Verify E-Heat switch is in off position, and DIP switches are set
properly.
J
3
Ensure no zones are calling by turning all thermostats off.
4
Apply 24 VAC Power to the 140202 2 Zone panel.
A
5
Verify green power LED near 24 VAC Terminals is lit.
A
6
Verify green heartbeat LED in middle of panel is pulsing.
A-B-H
7
Verify both zone LED's near damper terminals are green.
A-B-C
8
Switch zone 1 thermostat to heat mode, and call for heat in zone 1.
9
Verify zone 1 damper LED is green (open) and zone 2 damper LED is
red.
E-F
10
Verify heating system is operating, air is moving out zone 1 vents, and
zone 2 vents have minimal airflow.
F-G
11
Verify supply temp display measures heat change in supply air. Switch
zone 2 thermostat to heat mode, and call for heat in zone 2 by raising
set temperature above room temperature.
D
12
Verify zone 1 damper LED stays green (open) and zone 2 damper is
green
E
13
Verify heating system is operating and air is moving out into zone 1 and
2.
E-F-G
14
Return zone 1 thermostat to the off position. Verify zone 1 damper LED
turns red and zone 2 damper LED stay green.
E-F-G
15
Verify heating system is operating, air is moving out zone 2 vents, and
zone 1 vents have minimal airflow.
E-F-G
16
Turn zone 2 off. Verify system fan shuts off at the end of purge cycle.
H
17
Verify all zone LED's near damper terminals are green.
E-F-G-H
18
If the outside temperature is acceptable, repeat the above steps in
cooling mode. Cooling will not work if E-Heat is on.
19
When checkout is finished, restore thermostats and retest entire
system.
20
If the above steps do not solve the problem, please contact Technical
Summary of Contents for MaxAir 100e P2
Page 43: ...Page 43 WIRING DIAGRAM P2 UNITS...
Page 44: ...Page 44 WIRING DIAGRAM P3 UNITS...
Page 45: ...Page 45 WIRING DIAGRAM P2 UNITS ALTERATIONS HEAT PUMP OPTION...
Page 46: ...Page 46 WIRING DIAGRAM P3 UNITS ALTERATIONS HEAT PUMP OPTION...
Page 51: ...Page 51 FAN COIL DIMENSIONS AND RETURN AIR SIZE LOCATION...
Page 52: ...Page 52...
Page 53: ...Page 53...
Page 54: ...Page 54...
Page 55: ...Page 55...
Page 56: ...Page 56...
Page 61: ...Page 61 2 AND 2 5 TON EVAPORATOR COIL SIZES 70 IPCE 24 30A...
Page 62: ...Page 62 SAMPLE PIPING SCHEMATICS...
Page 63: ...Page 63...
Page 64: ...Page 64...
Page 65: ...Page 65...