Page 25
2.
SW3-1 IN “0-10V IN” SWITCH POSITION:
Selects
CONTINUOUSLY VARIABLE
outputs per table 3, below and the command (volume) level is input via the “0-10V IN”
connector:
L1,L2 SELECTIONS WHEN 0-10V INPUT ACTIVE
SET MAX
AIRFLOW
(DIP-SW2)
COMMAND INPUT
RANGE
COMMAND
OUTPUT RANGE
L1,L2=0
0-10V
0-100%
L1=1,L2=0
0-10V
0-83%
L1=0,L2=1
0-10V
0-66%
L1,L2=1
0-10V
0-50%
TABLE3
NOTE: POWER TO THE CONTROLLER MUST BE CYCLED FOR THE DISCRETE OR 0-
10V SWITCH STATE TO BE RECOGNIZED.
THE SELECTED STATE BECOMES
EFFECTIVE AFTER POWER IS RESTORED.
B.
ONE AND TWO STAGE HEATING SYSTEM SELECTOR
1.
"1&2-STG HT" (SW1-1):
In this position, single-stage and true two-stage heat
control from a thermostat is operational. The Heating inputs (W1, W2) will operate the
system as follows:
1.
OPERATING With a FURNACE ("Y" not Active in Heating)
D & W1 active
: When "1&2-Stg HT" and D AND W1 are active, the selected
output PWM % shown under W1 in TABLES A and B, above, occurs after a
15 sec delay after any W activates.
D & W2 active
: When "1&2-Stg HT" AND
D
AND
W2
are active, the selected
output PWM % shown under
W2
in TABLES A and B occurs after a 15 sec
time delay after W1 or W2 activate.
W2 has precedence over W
1: If either
W1
and
W2
, or
W2
alone, is active,
the
W2
command output occurs.
STAGING DELAY:
There is no time delay when sequentially staging from
W1 to W2 or back (i.e. without an OFF-CYCLE).
For convenience, when a single stage HEAT system is applied, an on-board
SHUNT
connects
W1
to W
2
for operation at the
W2
airflow whenever any W
is active.
NOTE: THE SHUNT MUST BE REMOVED WHEN A TWO STAGE HEATING SYSTEM IS
APPLIED.
Summary of Contents for MaxAir 100e P2
Page 43: ...Page 43 WIRING DIAGRAM P2 UNITS...
Page 44: ...Page 44 WIRING DIAGRAM P3 UNITS...
Page 45: ...Page 45 WIRING DIAGRAM P2 UNITS ALTERATIONS HEAT PUMP OPTION...
Page 46: ...Page 46 WIRING DIAGRAM P3 UNITS ALTERATIONS HEAT PUMP OPTION...
Page 51: ...Page 51 FAN COIL DIMENSIONS AND RETURN AIR SIZE LOCATION...
Page 52: ...Page 52...
Page 53: ...Page 53...
Page 54: ...Page 54...
Page 55: ...Page 55...
Page 56: ...Page 56...
Page 61: ...Page 61 2 AND 2 5 TON EVAPORATOR COIL SIZES 70 IPCE 24 30A...
Page 62: ...Page 62 SAMPLE PIPING SCHEMATICS...
Page 63: ...Page 63...
Page 64: ...Page 64...
Page 65: ...Page 65...