background image

IO-123114 Effective 12-04-2014

11

Below are brief descriptions of the key components of the unit and in-

stallation. This manual only provides general idea of the components 

and recommended practices. The installer should use best judge-

ment to ensure safe installation and operation of the unit.

1.

 Room Thermostat- This is the device that controls that operation 

of your heating and/or cooling unit. It senses the indoor temperature 

and signals the equipment to start or stop maintaining the tempera-

ture you have selected for your comfort. The room thermostat should 

be in a central, draft free inside wall location for best operation. Do 

not place any heat producing apparatus such as lights, radio, etc., 

near the thermostat as this will cause erratic operation of the comfort 

system. The thermostat can accumulate dust or lint which can affect 

its accuracy. It should be cleaned annually.

2.

 Air Filter(s) - All central air moving comfort systems must include 

air filter(s). These filters will be located either in the equipment or in 

the return air duct system upstream of the equipment. The filter(s) 

removes dust and debris from the air thus helping to keep your air-

conditioned space clean. More important, the filter keeps dust and 

debris from collecting on the heat transfer surfaces thus maintaining 

18. Operation and Maintenance

4. a) Do not store combustible materials 

or use gasoline or other flammable liquids 

or vapors in the vicinity of this appliance. 

b) Do not operate the comfort equipment with panels re-

moved.

c) Have your contractor point out and identify the various 

cut-off devices, switches, etc., that serve your comfort 

equipment. There is a main switch that will cut off energy to 

your heating system. Know where they are so that you may 

cut off the flow of energy in the event of overheating.

!

WARNING

optimum equipment efficiency and performance. Inspect and clean 

or replace filters every month. This routine maintenance procedure 

will pay big dividends in reduced operating cost and reduced service 

expense. Never operate comfort equipment without filter(s).

3.

 Fuses and/or Circuit Breakers- This comfort equipment should be 

connected to the building electric service in accordance with local 

and National Electric codes. This electrical connection will include 

over-current protection in the form of circuit breakers. Have your 

contractor identify the circuits and the location of over-current protec-

tion so that you will be in a position to make inspections or replace-

ments in the event the equipment fails to operate.

19. Final System Checkout

1. 

Make certain all cabinet openings are properly sealed and any 

grommets moved during installation are moved into proper place. 

2. 

With cooling system operating, check for condensate leakage.

3. 

Perform leak detection inspection of refrigerant circuit and con-

necting piping. 

4.

 Secure all cabinet doors.

5.

 Periodic Checkup and Service- This product is designed to pro-

vide many years of dependable, trouble-free comfort when properly 

maintained. Proper maintenance will consist of annual check-ups 

and cleaning of the internal electrical and heat transfer components 

by a qualified service technician. Failure to provide periodic checkup 

and  cleaning  can  result  in  excessive  operating  cost  and/or  equip

-

ment malfunction.

6.

 Lubrication- Direct drive blower motors are equipped with perma-

nently lubricated bearings and do not require further lubrication.

7.

 Air filter replacement: An air filter can restrict the airflow of air to 

the fan coil if it is not cleaned or replaced periodically. When replac-

ing the air filter, always replace with the same type and size as origi

-

nally furnished with the unit.

Summary of Contents for GAS Series

Page 1: ...r service personnel CAUTION CAUTION WARNING WARNING WARNING WARNING WARNING WARNING GAT GAS Series Horizontal Ceiling Mount Electric Heat Dx Cool Air Handler 2 Introduction The GAT GAS Series air hand...

Page 2: ...vel All main supply and return air drops should be properly size as deter mined by the designer of the duct system and should not necessarily be the size of the duct flange openings of the unit The dr...

Page 3: ...burr free and clean Failure to do so may increase chances of a leak It is recommended to use a pipe cutter to remove the spun closed end of the suction line To reduce air leakage rubber gommets may b...

Page 4: ...nstructions are separated into sec tions by metering device 2 A ducted return requires a non louvered panel 1 A bottom return installation requires a louvered panel 3 Both louvered and non louvered pa...

Page 5: ...eflon O ring is located between the two halves of the flowrator CAUTION I 2 Replace the Teflon O ring located between the halves Discard Schrader if present During some installations a piston change m...

Page 6: ...to install the right valve can lead to poor per formance and possible compressor damage CAUTION Ensure that the TXV bulb is in direct con tact with the suction vapor line Gap be tween the bulb and tub...

Page 7: ...to the liquid line stub out See 8A I 3 Do not attempt to touch brazed joints while hot Severe burns may result WARNING III 3 After ensuring that the Teflon O ring seal is still in place inside the flo...

Page 8: ...connections using proper brazing pro cedures 9 When all line connections are brazed perform a proper system evacuation procedure per the outdoor unit manufacturer instructions 10 Seal the penetration...

Page 9: ...t 42 61 S Small Cabinet 18 36 Heat Strip 00 NO Heat BLOWER DATA UNIT MODEL RPM AMP VOLT HP CFM VS STATIC PRESSURE 0 00 0 10 0 20 0 30 0 40 GAT 18 1625 1 4 240 1 4 850 775 700 675 600 GAT 24 1000 900 8...

Page 10: ...ssure measuring device 0 1 0 in slope gauge and a tempera ture measuring device 0 200 F thermometer 3 Release system charge from outdoor unit and call for cooling 4 Use outdoor unit equipment manufact...

Page 11: ...are so that you may cut off the flow of energy in the event of overheating WARNING optimum equipment efficiency and performance Inspect and clean or replace filters every month This routine maintenanc...

Page 12: ...MER 24 VOLTS HTR 3 BK CB CB LC LC HS LO SPEED CAPPED MED SPEED CAPPED HS HS BLOWER MOTOR SPEED SETTING FOR MAX KW RATING UNIT MODEL MAX KW SPEED TAP ELECTRIC HEAT ONLY ELECTRIC HEAT HEAT PUMP MAX KW S...

Page 13: ...IO 123114 Effective 12 04 2014 13...

Page 14: ...Atascocita Rd Humble TX 77396 Phone 281 441 6500 Toll Free 800 423 9007 Fax 281 441 6510 www airmark ac com Copyright 2014 AirMark All Rights Reserved Revised 12 04 2014 Subject to change without not...

Reviews: