background image

10

IO-123114 Effective 12-04-2014

1.

 Bring airflow up to the maximum CFM possible according to Table 

11A-1.

2.

 Evacuate refrigeration system to micron level required by outdoor 

unit manufacturer.

14. System Charging

An improperly charged system may cause 

degradation in system performance and 

damage the compressor. After installation 

of the coil, refer to the outdoor unit manufacturer for charging 

techniques and amount of charge. If outdoor unit manufacturers 

charging instructions are unavailable, then refer to instructions 

below to charge the system.

CAUTION

!

16. Start-Up

14B . Expansion Valve Coils

Add refrigerant until the subcooling measured at the outdoor unit 

liquid line matches the subcooling recommendation of the outdoor 

manufacturer  (typically  7º  –  10º  F).  If  chart  is  unavailable  refer  to 

Table 14B-1.

Table 14B-1.

After all connections are made, start-up and checkout must be per-

formed before proper evaluation of the entire system can be made. 

Make sure that heat anticipator is properly set as noted on thermo-

stat instructions. Load requirements can vary in each residence and 

it may be necessary for the installer or homeowner to make slight ad-

justments to the heat anticipator setting for longer or shorter cycles. 

It is recommended to change the setting no more than plus or minus 

0.05 amps at a time. Greater changes can cause the unit to rapid 

cycle or remain on excessively.

15. Adjustment Of Heat Anticipator

14A . Flowrator Coils

Add refrigerant until the superheat measured at the outdoor unit suc-

tion/vapor line matches the superheat listed in Table 14B-1.

To properly check the unit’s operation, the installer should have an 

electrical current measuring device (0-10 amp Amprobe, Fluke), air 

pressure measuring device (0-1.0 in slope gauge), and a tempera-

ture-measuring device (0-200ºF thermometer).  

3.

 Release system charge from outdoor unit and call for cooling.

4.

 Use outdoor unit equipment manufacturer specific charging charts 

if available and make proper charge adjustment based upon outdoor 

unit instructions. 

5.

 If outdoor unit instructions and charts are not available, use Aspen 

provided charts. Make certain indoor air temperature is near comfort 

level setpoint of 75°F prior to establishing superheat and subcooling 

levels. 

Install the Amprobe to measure blower current, the slope gauge to 

measure static air pressure at the units and the temperature device 

to measure unit supply and return air temperature. Before taking 

measurements, be sure that all registers, grilles and dampers are 

open or set to their proper positions. Be sure that clean filters are 

in place. Temperature measuring device must be installed to obtain 

average temperature at both inlet and outlet. For outlet, measure 

temperature of each main trunk at a location far enough away to 

avoid heater radiation and read the average temperatures. Table 

11A-1 shows the CFM that should be achieved at various external 

static pressures

Turn on power supply. Set thermostat fan switch to on. Set the cool-

ing indicator to maximum, heating to minimum. System switch may 

be on heat or cool. Check slope gauge measurement against appro-

priate air flow chart. Make damper, register and motor speed adjust

-

ments to obtain required airflow.

Set thermostat fan switch to auto, system to heat and thermostat 

heating indicator to maximum heat. Blower should start and all heat 

be energized.

Check air flow using temperature rise method.

17. Checking Air Flow/Temperature Rise Method 

CFM OUTPUT BTUH

TEMP RISE

=

(

)

.

.

1 08

NOTE: 

BTUH output should be computed by VOLT x AMPS x 3.4 = 

BTUH OUTPUT. Since line volt can vary, do not use nameplate rat

-

ing to determine output.

Summary of Contents for GAS Series

Page 1: ...r service personnel CAUTION CAUTION WARNING WARNING WARNING WARNING WARNING WARNING GAT GAS Series Horizontal Ceiling Mount Electric Heat Dx Cool Air Handler 2 Introduction The GAT GAS Series air hand...

Page 2: ...vel All main supply and return air drops should be properly size as deter mined by the designer of the duct system and should not necessarily be the size of the duct flange openings of the unit The dr...

Page 3: ...burr free and clean Failure to do so may increase chances of a leak It is recommended to use a pipe cutter to remove the spun closed end of the suction line To reduce air leakage rubber gommets may b...

Page 4: ...nstructions are separated into sec tions by metering device 2 A ducted return requires a non louvered panel 1 A bottom return installation requires a louvered panel 3 Both louvered and non louvered pa...

Page 5: ...eflon O ring is located between the two halves of the flowrator CAUTION I 2 Replace the Teflon O ring located between the halves Discard Schrader if present During some installations a piston change m...

Page 6: ...to install the right valve can lead to poor per formance and possible compressor damage CAUTION Ensure that the TXV bulb is in direct con tact with the suction vapor line Gap be tween the bulb and tub...

Page 7: ...to the liquid line stub out See 8A I 3 Do not attempt to touch brazed joints while hot Severe burns may result WARNING III 3 After ensuring that the Teflon O ring seal is still in place inside the flo...

Page 8: ...connections using proper brazing pro cedures 9 When all line connections are brazed perform a proper system evacuation procedure per the outdoor unit manufacturer instructions 10 Seal the penetration...

Page 9: ...t 42 61 S Small Cabinet 18 36 Heat Strip 00 NO Heat BLOWER DATA UNIT MODEL RPM AMP VOLT HP CFM VS STATIC PRESSURE 0 00 0 10 0 20 0 30 0 40 GAT 18 1625 1 4 240 1 4 850 775 700 675 600 GAT 24 1000 900 8...

Page 10: ...ssure measuring device 0 1 0 in slope gauge and a tempera ture measuring device 0 200 F thermometer 3 Release system charge from outdoor unit and call for cooling 4 Use outdoor unit equipment manufact...

Page 11: ...are so that you may cut off the flow of energy in the event of overheating WARNING optimum equipment efficiency and performance Inspect and clean or replace filters every month This routine maintenanc...

Page 12: ...MER 24 VOLTS HTR 3 BK CB CB LC LC HS LO SPEED CAPPED MED SPEED CAPPED HS HS BLOWER MOTOR SPEED SETTING FOR MAX KW RATING UNIT MODEL MAX KW SPEED TAP ELECTRIC HEAT ONLY ELECTRIC HEAT HEAT PUMP MAX KW S...

Page 13: ...IO 123114 Effective 12 04 2014 13...

Page 14: ...Atascocita Rd Humble TX 77396 Phone 281 441 6500 Toll Free 800 423 9007 Fax 281 441 6510 www airmark ac com Copyright 2014 AirMark All Rights Reserved Revised 12 04 2014 Subject to change without not...

Reviews: