7. Connecting Ducting

8. Metering Devices/Liquid Line Connection

1. 

Secure the supply air ducting to the duct flange of the air handler. 

Canvas connectors are recommended for reducing potential noise 

transmission.

Aspen coils are available with two kinds of metering devices a) flow

-

rator or b) TXV. The following instructions are separated into sec

-

tions by metering device. 

2. A ducted return requires a non-louvered panel.

1. A bottom return installation requires a louvered panel.

3. Both louvered and non-louvered panels are mounted to the ceiling 

using screws.

7B. Bottom Return

1. To connect return air ducting to the air handler, remove the knock-

out on the rear side of the enclosure to install the ducting.

7A. Remote/Ducted Return

6. Reinstall the components removed prior to mounting the enclo

-

sure.

Fig 8A-1.  Flowrator assembly components

8A.  Flowrator Coils

Summary of Contents for GAS Series

Page 1: ...r service personnel CAUTION CAUTION WARNING WARNING WARNING WARNING WARNING WARNING GAT GAS Series Horizontal Ceiling Mount Electric Heat Dx Cool Air Handler 2 Introduction The GAT GAS Series air hand...

Page 2: ...vel All main supply and return air drops should be properly size as deter mined by the designer of the duct system and should not necessarily be the size of the duct flange openings of the unit The dr...

Page 3: ...burr free and clean Failure to do so may increase chances of a leak It is recommended to use a pipe cutter to remove the spun closed end of the suction line To reduce air leakage rubber gommets may b...

Page 4: ...nstructions are separated into sec tions by metering device 2 A ducted return requires a non louvered panel 1 A bottom return installation requires a louvered panel 3 Both louvered and non louvered pa...

Page 5: ...eflon O ring is located between the two halves of the flowrator CAUTION I 2 Replace the Teflon O ring located between the halves Discard Schrader if present During some installations a piston change m...

Page 6: ...to install the right valve can lead to poor per formance and possible compressor damage CAUTION Ensure that the TXV bulb is in direct con tact with the suction vapor line Gap be tween the bulb and tub...

Page 7: ...to the liquid line stub out See 8A I 3 Do not attempt to touch brazed joints while hot Severe burns may result WARNING III 3 After ensuring that the Teflon O ring seal is still in place inside the flo...

Page 8: ...connections using proper brazing pro cedures 9 When all line connections are brazed perform a proper system evacuation procedure per the outdoor unit manufacturer instructions 10 Seal the penetration...

Page 9: ...t 42 61 S Small Cabinet 18 36 Heat Strip 00 NO Heat BLOWER DATA UNIT MODEL RPM AMP VOLT HP CFM VS STATIC PRESSURE 0 00 0 10 0 20 0 30 0 40 GAT 18 1625 1 4 240 1 4 850 775 700 675 600 GAT 24 1000 900 8...

Page 10: ...ssure measuring device 0 1 0 in slope gauge and a tempera ture measuring device 0 200 F thermometer 3 Release system charge from outdoor unit and call for cooling 4 Use outdoor unit equipment manufact...

Page 11: ...are so that you may cut off the flow of energy in the event of overheating WARNING optimum equipment efficiency and performance Inspect and clean or replace filters every month This routine maintenanc...

Page 12: ...MER 24 VOLTS HTR 3 BK CB CB LC LC HS LO SPEED CAPPED MED SPEED CAPPED HS HS BLOWER MOTOR SPEED SETTING FOR MAX KW RATING UNIT MODEL MAX KW SPEED TAP ELECTRIC HEAT ONLY ELECTRIC HEAT HEAT PUMP MAX KW S...

Page 13: ...IO 123114 Effective 12 04 2014 13...

Page 14: ...Atascocita Rd Humble TX 77396 Phone 281 441 6500 Toll Free 800 423 9007 Fax 281 441 6510 www airmark ac com Copyright 2014 AirMark All Rights Reserved Revised 12 04 2014 Subject to change without not...

Reviews: