background image

6

IO-123114 Effective 12-04-2014

Be aware of the Teflon O-ring. Be sure to 

replace the O-ring to attain a proper

seal. (The Teflon O-ring is located between 

the two halves of the flowrator)

CAUTION

!

Pay close attention to the piston orienta-

tion. The pointed end of the piston MUST 

go into the distributor body, towards the 

coil. Failure to ensure this orientation will cause the piston 

to be bypassed during operation which might damage the 

outdoor unit.

CAUTION

!

II-6.

 Replace the piston with one 

of the correct size. Do not force 

the new piston into the body.  

Make sure the piston moves 

freely in body.

II-7.

 Assemble the two halves correctly and ensure that the white 

Teflon O-ring is present between the two halves (See I-5).  Slide the 

13/16” nut onto the distributor body.

II-8.

 Tighten the nut to a torque of approximately 10-30 ft-lbs. 

Do NOT 

overtighten the nut. Overtightening will impede the piston movement 

during operation.

II-9.

 If present, slide the rubber grommet back to position to prevent 

air leakage.

8B.  TXV Coils

Ensure that the TXV selected is compat-

ible with the refrigerant used in the out-

door system (R22 or R410A). TXV caps are 

painted green for R22 or pink for R410A. In absence of col-

or, the caps will be marked with the compatible refrigerant.

CAUTION

!

The sensing bulb and TXV body MUST be 

protected from overheating during braz-

ing.  The sensing bulb and TXV body must 

be covered using a quench cloth or wet cloth when brazing. 

Pointing the brazing flame away from the valve and sensing 

bulb provide partial protection only.

!

WARNING

Fig 8B-1.  Components of a typical TXV assembly

The valves should be sized according to 

the capacity of the outdoor unit. Failure to 

install the right valve can lead to poor per-

formance and possible compressor damage.

CAUTION

!

Ensure that the TXV bulb is in direct con-

tact with the suction/vapor line. Gap be-

tween the bulb and tube should be avoid-

ed. Failure to do so will impair the proper functioning of the 

TXV valve.

CAUTION

!

I. TXV Bulb Horizontal Mounting

The orientation and location of the TXV bulb has a major influence 

on the system performance.

It  is  recommended  that  the  TXV  bulb  be  installed  parallel  to  the 

ground (on a horizontal plane). The bulb position should be above 

and between 4 o’clock and 8 o’clock. Fig. 8B-2 shows the recom-

mended position for the TXV bulb installation in the horizontal plane.

The TXV sensing bulb SHOULD be mounted on the suction line ap

-

proximately 6” from the TXV or coil housing using the metal clamp 

provided. In order to obtain a good temperature reading and correct 

superheat control, the TXV sensing bulb must conform to ALL of the 

following criteria:

 

1. The sensing bulb 

MUST

 be in direct and continuous 

 

contact with the suction line.

 

2. The sensing bulb should be mounted horizontally on 

 

the suction line.

 

3. The sensing bulb 

MUST

 be mounted above and between

 

the 4 and 8 o’clock position on the circumference of the 

 

suction line.

 

4. The sensing bulb 

MUST

 be insulated from outside air.

A properly mounted sensing bulb will prevent false readings caused 

by liquid refrigerant that may have formed inside the suction/vapor 

line. Insulation will protect the sensing bulb from false readings due 

to contact with warm air.

Fig 8B-2.  Recommended location for horizontal TXV bulb mount

II-5.

 Pull the piston out using a 

small wire or pick. Verify the pis

-

ton size (size is typically stamped 

on the body of the piston - Fig 

8A-2). If a different piston size 

is required by the outdoor unit 

manufacturer, replace the piston 

using the small wire provided with 

the piston kit.

Summary of Contents for GAS Series

Page 1: ...r service personnel CAUTION CAUTION WARNING WARNING WARNING WARNING WARNING WARNING GAT GAS Series Horizontal Ceiling Mount Electric Heat Dx Cool Air Handler 2 Introduction The GAT GAS Series air hand...

Page 2: ...vel All main supply and return air drops should be properly size as deter mined by the designer of the duct system and should not necessarily be the size of the duct flange openings of the unit The dr...

Page 3: ...burr free and clean Failure to do so may increase chances of a leak It is recommended to use a pipe cutter to remove the spun closed end of the suction line To reduce air leakage rubber gommets may b...

Page 4: ...nstructions are separated into sec tions by metering device 2 A ducted return requires a non louvered panel 1 A bottom return installation requires a louvered panel 3 Both louvered and non louvered pa...

Page 5: ...eflon O ring is located between the two halves of the flowrator CAUTION I 2 Replace the Teflon O ring located between the halves Discard Schrader if present During some installations a piston change m...

Page 6: ...to install the right valve can lead to poor per formance and possible compressor damage CAUTION Ensure that the TXV bulb is in direct con tact with the suction vapor line Gap be tween the bulb and tub...

Page 7: ...to the liquid line stub out See 8A I 3 Do not attempt to touch brazed joints while hot Severe burns may result WARNING III 3 After ensuring that the Teflon O ring seal is still in place inside the flo...

Page 8: ...connections using proper brazing pro cedures 9 When all line connections are brazed perform a proper system evacuation procedure per the outdoor unit manufacturer instructions 10 Seal the penetration...

Page 9: ...t 42 61 S Small Cabinet 18 36 Heat Strip 00 NO Heat BLOWER DATA UNIT MODEL RPM AMP VOLT HP CFM VS STATIC PRESSURE 0 00 0 10 0 20 0 30 0 40 GAT 18 1625 1 4 240 1 4 850 775 700 675 600 GAT 24 1000 900 8...

Page 10: ...ssure measuring device 0 1 0 in slope gauge and a tempera ture measuring device 0 200 F thermometer 3 Release system charge from outdoor unit and call for cooling 4 Use outdoor unit equipment manufact...

Page 11: ...are so that you may cut off the flow of energy in the event of overheating WARNING optimum equipment efficiency and performance Inspect and clean or replace filters every month This routine maintenanc...

Page 12: ...MER 24 VOLTS HTR 3 BK CB CB LC LC HS LO SPEED CAPPED MED SPEED CAPPED HS HS BLOWER MOTOR SPEED SETTING FOR MAX KW RATING UNIT MODEL MAX KW SPEED TAP ELECTRIC HEAT ONLY ELECTRIC HEAT HEAT PUMP MAX KW S...

Page 13: ...IO 123114 Effective 12 04 2014 13...

Page 14: ...Atascocita Rd Humble TX 77396 Phone 281 441 6500 Toll Free 800 423 9007 Fax 281 441 6510 www airmark ac com Copyright 2014 AirMark All Rights Reserved Revised 12 04 2014 Subject to change without not...

Reviews: