background image

IO-123114 Effective 12-04-2014

5

Note: Photos are for basic illustration purposes only.  Actual equip-

ment configuration may differ from that shown.

Use Piston sizes recommended by the 

outdoor unit manufacturer whenever pos-

sible. The piston should be sized accord-

ing to the capacity of the outdoor unit.

CAUTION

!

Failure to install the proper piston can 

lead to poor system performance and 

possible compressor damage.

!

WARNING

I. Installation

I-1.

 Disassemble flowrator body 

using two wrenches and un-

screwing with a counterclockwise 

motion. 

I-4.

 Braze the stub-out portion to the liquid line and let cool.

I-3.

 Slide the attachment nut onto 

the liquid line stub out.

I-6.

 Tighten the nut to a torque of approximately 10-30 ft-lbs. 

Do NOT 

overtighten the nut. Overtightening will impede the piston movement 

during operation.

I-5.

 Taking care that the white 

Teflon seal is still in place inside 

the flowrater body, firmly seat the 

stub and screw the attachment 

nut to flowrater body.

Be aware of the Teflon O-ring. Be sure to 

replace the O-ring to attain a proper

seal. (The Teflon O-ring is located between 

the two halves of the flowrator)

CAUTION

!

I-2.

 Replace the Teflon O-ring 

(located between the halves). 

Discard Schrader if present.

During some installations, a piston change may 

be required. If so, the installer 

MUST

 change the 

piston.  Use piston sizes recommended by the 

outdoor unit manufacturer. If a sizing chart is not 

available, use the piston size chart provided be-

low to size the required piston. The size of the 

piston is stamped on the piston body (Fig 8A-2). 

II. Piston Replacement

Fig 8A-2

Use the chart below when matching coil with an outdoor unit with a 

different nominal capacity than the coil.

Note: Photos are for basic illustration purposes only.  Actual equip-

ment configuration may differ from that shown.

II-4.

 Slide the 13/16” nut over 

the lineset and separate the two 

halves of the flowrator.

II-1.

 Evacuate the system as per manufacturer guidelines and rec-

ommendations

II-2.

 Turn the 13/16” nut once to release any residual pressure in the 

coil.

II-3.

 After ensuring that the coil 

is free of any residual pressure, 

disassemble the flowrator body 

completely using two wrenches. 

Take great care not to distort the 

feeder tubes. The wrench used 

to clasp the nut should be turned 

in counter-clockwise direction to 

unscrew the nut.

Summary of Contents for GAS Series

Page 1: ...r service personnel CAUTION CAUTION WARNING WARNING WARNING WARNING WARNING WARNING GAT GAS Series Horizontal Ceiling Mount Electric Heat Dx Cool Air Handler 2 Introduction The GAT GAS Series air hand...

Page 2: ...vel All main supply and return air drops should be properly size as deter mined by the designer of the duct system and should not necessarily be the size of the duct flange openings of the unit The dr...

Page 3: ...burr free and clean Failure to do so may increase chances of a leak It is recommended to use a pipe cutter to remove the spun closed end of the suction line To reduce air leakage rubber gommets may b...

Page 4: ...nstructions are separated into sec tions by metering device 2 A ducted return requires a non louvered panel 1 A bottom return installation requires a louvered panel 3 Both louvered and non louvered pa...

Page 5: ...eflon O ring is located between the two halves of the flowrator CAUTION I 2 Replace the Teflon O ring located between the halves Discard Schrader if present During some installations a piston change m...

Page 6: ...to install the right valve can lead to poor per formance and possible compressor damage CAUTION Ensure that the TXV bulb is in direct con tact with the suction vapor line Gap be tween the bulb and tub...

Page 7: ...to the liquid line stub out See 8A I 3 Do not attempt to touch brazed joints while hot Severe burns may result WARNING III 3 After ensuring that the Teflon O ring seal is still in place inside the flo...

Page 8: ...connections using proper brazing pro cedures 9 When all line connections are brazed perform a proper system evacuation procedure per the outdoor unit manufacturer instructions 10 Seal the penetration...

Page 9: ...t 42 61 S Small Cabinet 18 36 Heat Strip 00 NO Heat BLOWER DATA UNIT MODEL RPM AMP VOLT HP CFM VS STATIC PRESSURE 0 00 0 10 0 20 0 30 0 40 GAT 18 1625 1 4 240 1 4 850 775 700 675 600 GAT 24 1000 900 8...

Page 10: ...ssure measuring device 0 1 0 in slope gauge and a tempera ture measuring device 0 200 F thermometer 3 Release system charge from outdoor unit and call for cooling 4 Use outdoor unit equipment manufact...

Page 11: ...are so that you may cut off the flow of energy in the event of overheating WARNING optimum equipment efficiency and performance Inspect and clean or replace filters every month This routine maintenanc...

Page 12: ...MER 24 VOLTS HTR 3 BK CB CB LC LC HS LO SPEED CAPPED MED SPEED CAPPED HS HS BLOWER MOTOR SPEED SETTING FOR MAX KW RATING UNIT MODEL MAX KW SPEED TAP ELECTRIC HEAT ONLY ELECTRIC HEAT HEAT PUMP MAX KW S...

Page 13: ...IO 123114 Effective 12 04 2014 13...

Page 14: ...Atascocita Rd Humble TX 77396 Phone 281 441 6500 Toll Free 800 423 9007 Fax 281 441 6510 www airmark ac com Copyright 2014 AirMark All Rights Reserved Revised 12 04 2014 Subject to change without not...

Reviews: