background image

8

IO-123114 Effective 12-04-2014

9. Connecting Refrigerant Lines

1.

  Release  nitrogen  hold

-

ing charge by depressing the 

Shrader Valve at the liquid line 

connection on the air handler. 

If  no  gas  releases  from  the  air 

handler, contact distributor re-

garding potential leak.

2.

 Cut off Shrader Valve fitting at 

the liquid line connection.  Use a 

tubing cutter for this step. Clean 

the burr from the cut tubing to 

reduce the chance of future 

leaks. Connect the liquid line to 

the tubing at the indoor unit.

3.

 Use a tubing cutter to remove 

the spun end from the suction 

line connection at the air han-

dler. Clean the burr from the cut 

tubing to reduce the chance of 

future leaks.

4.

  To avoid heat damage to grommets where present, remove these 

prior to brazing by sliding them over the refrigerant lines and out of 

the way.

5. 

Check to determine if the 

evaporator coil has a Shrader 

fitting  on  the  suction  manifold. 

If  yes,  remove  the  valve  core 

to prevent heat damage during 

brazing. Replace the valve core 

once the piping has cooled.

6. 

If the air handler has a TXV metering device, remove the sensing 

bulb from the suction line prior to brazing to prevent heat damage 

from occurring. Replace the sensing bulb once the piping has cooled.

7.  Flow nitrogen through the piping when brazing.
8.  Braze both refrigerant line connections using proper brazing pro-

cedures.
9.  When all line connections are brazed, perform a proper system 

evacuation procedure per the outdoor unit manufacturer instructions.

10. 

Seal the penetration openings where the lineset piping enters the 

air handler cabinet. 

1. 

Following outdoor unit manufacturer instructions and recommen-

dations, charge the system with dry nitrogen to a maximum pressure 

of 150 PSIG.

3.

  If any leaks are discovered, relieve system pressure and repair 

leaks.  Repeat steps 1-3.

4.

 With no leaks or weak connections present,  evacuate the system 

and charge as per the outdoor unit manufacturer instructions and 

specifications. 

10. Leak Check

2. 

Check all brazed and screw-

on line connections by applying a 

soap solution to the joint.  A leak 

will produce bubbles in the soap 

solution.

11. Electrical Installation

These units are designed for a single phase 208/240 volts, 60 Hz 

power supply. Wire selection and wiring must be in accordance with 

the  National  Electric  Code  and/or  local  codes.  Unit  terminals  are 

designed to accommodate copper or aluminum wiring. If aluminum 

wiring is used; please observe special precautions relative to sizing, 

wire connections and corrosion protection.

Fig.11-1 shows the typical electrical connections required for A/C 

only and heat pump applications.

All models with 3, 5, 8 or 10 kW electric heat are arranged for single 

circuit connections. Fig. 11A-2 shows the typical electrical connec-

tions required for A/C only and heat pump applications.

Fig 11-1.

Summary of Contents for GAS Series

Page 1: ...r service personnel CAUTION CAUTION WARNING WARNING WARNING WARNING WARNING WARNING GAT GAS Series Horizontal Ceiling Mount Electric Heat Dx Cool Air Handler 2 Introduction The GAT GAS Series air hand...

Page 2: ...vel All main supply and return air drops should be properly size as deter mined by the designer of the duct system and should not necessarily be the size of the duct flange openings of the unit The dr...

Page 3: ...burr free and clean Failure to do so may increase chances of a leak It is recommended to use a pipe cutter to remove the spun closed end of the suction line To reduce air leakage rubber gommets may b...

Page 4: ...nstructions are separated into sec tions by metering device 2 A ducted return requires a non louvered panel 1 A bottom return installation requires a louvered panel 3 Both louvered and non louvered pa...

Page 5: ...eflon O ring is located between the two halves of the flowrator CAUTION I 2 Replace the Teflon O ring located between the halves Discard Schrader if present During some installations a piston change m...

Page 6: ...to install the right valve can lead to poor per formance and possible compressor damage CAUTION Ensure that the TXV bulb is in direct con tact with the suction vapor line Gap be tween the bulb and tub...

Page 7: ...to the liquid line stub out See 8A I 3 Do not attempt to touch brazed joints while hot Severe burns may result WARNING III 3 After ensuring that the Teflon O ring seal is still in place inside the flo...

Page 8: ...connections using proper brazing pro cedures 9 When all line connections are brazed perform a proper system evacuation procedure per the outdoor unit manufacturer instructions 10 Seal the penetration...

Page 9: ...t 42 61 S Small Cabinet 18 36 Heat Strip 00 NO Heat BLOWER DATA UNIT MODEL RPM AMP VOLT HP CFM VS STATIC PRESSURE 0 00 0 10 0 20 0 30 0 40 GAT 18 1625 1 4 240 1 4 850 775 700 675 600 GAT 24 1000 900 8...

Page 10: ...ssure measuring device 0 1 0 in slope gauge and a tempera ture measuring device 0 200 F thermometer 3 Release system charge from outdoor unit and call for cooling 4 Use outdoor unit equipment manufact...

Page 11: ...are so that you may cut off the flow of energy in the event of overheating WARNING optimum equipment efficiency and performance Inspect and clean or replace filters every month This routine maintenanc...

Page 12: ...MER 24 VOLTS HTR 3 BK CB CB LC LC HS LO SPEED CAPPED MED SPEED CAPPED HS HS BLOWER MOTOR SPEED SETTING FOR MAX KW RATING UNIT MODEL MAX KW SPEED TAP ELECTRIC HEAT ONLY ELECTRIC HEAT HEAT PUMP MAX KW S...

Page 13: ...IO 123114 Effective 12 04 2014 13...

Page 14: ...Atascocita Rd Humble TX 77396 Phone 281 441 6500 Toll Free 800 423 9007 Fax 281 441 6510 www airmark ac com Copyright 2014 AirMark All Rights Reserved Revised 12 04 2014 Subject to change without not...

Reviews: