IO-123114 Effective 12-04-2014

1

INSTALLATION GUIDE

1. Safety Instruction

!

WARNING

Potential safety hazards are alerted using the following symbols. The symbol is used in conjunction with terms 

that indicate the intensity of the hazard.

This symbol indicates a potentially hazardous situation, which if not avoided, 

could result in serious injury, property damage, product damage or death.

Certified technicians or those individuals 

meeting  the  requirements  specified  by 

NATE may use this information. Property 

and product damage or personal injury hazard may occur 

without such background.

All power sources should be disconnect-

ed prior to servicing. Failure to do so may 

cause personal injury or property dam-

age.

Product designed and manufactured to 

permit installation in accordance with lo-

cal and national building codes. It is the 

installer’s responsibility to ensure that product is installed 

in strict compliance with national and local codes. Manufac-

turer takes no responsibility for damage (personal, product 

or property) caused due to installations violating regula-

tions. In absence of local/state codes, refer to National Elec-

tric Code: NFPA 90A & 90B Uniform Mechanical Code.

When this unit is installed in an enclosed 

area, such as a garage or utility room with 

any Carbon Monoxide producing devices 

(i.e. automobile, space heater, water heater etc.) ensure that 

the enclosed area is properly ventilated.

The unit is designed for operation with 

208/240 V, single phase, 60 Hz power sup-

ply. Aspen will not be reponsible for dam-

ages caused due to modification of the unit to operate with 

alternative power sources.

Unit is not approved for outdoor installa-

tions.

This symbol indicates a potentially hazardous situation, which if not avoided, 

may result in moderate injury or property damage.

Only factory authorized kits and acces-

sories should be used when installing or 

modifying this unit unless it is so noted in 

these instructions. Some localities may require a licensed 

installer/service personnel.

CAUTION

!

CAUTION

!

!

WARNING

!

WARNING

!

WARNING

!

WARNING

!

WARNING

!

WARNING

GAT & GAS Series - Horizontal Ceiling 

Mount Electric Heat Dx Cool Air Handler

2. Introduction

The GAT & GAS Series air handlers are versatile horizontal ceiling 

mount units. These air handlers have the following standard features:

Louvered ceiling access panel has separate frame that attaches to 

ceiling joists. Solid access panel available for use with end return 

installations. Compatible with most brands of air conditioners or heat 

pumps.

I. Application Versatility

II. Motor

Direct drive multi-speed blowers circulate air quietly and efficiently. 

2-speed motors allow for precise air volume selection. Motor speeds 

can be easily selected via motor terminals. Blowers are mounted on 

a plate so they can be easily removed for service.

III. Cabinet (GAT Only)

Sturdy, fully insulated galvanized steel cabinet with painted front 

panels. Knockout for duct return.

IV. Modular Electric Heat Kits

Heat kits available with either circuit breakers or terminal blocks. 

Available in 3, 4, 5, 6, 8, & 10 KW. Models with electric heat include 

sequencers and temperature limit switches for safe, efficient opera

-

tion. Modules are easily installed in the field using molex plugs or 

can be ordered factoryinstalled. Easily accessible controls for quick 

service. Electrical connections can be made from the top or left. Dis-

connect does not protrude through the wall panel. Fan time delay 

relay standard for increased efficiency.

V. Electronic Circuit Board

Electronic circuit board provides 30 secs ON/OFF blower time delay 

extracting more heat/cool from the coil.

VI. DX Coil

High efficiency rifled copper tubes/enhanced aluminum fins provide 

maximum heat transfer. All coils immersion tested at 500 psi then ni

-

trogen pressurized and factory sealed for maximum reliability. Liquid-

line Schrader allows pre-installation pressure testing. Available with 

either orifice or TXV metering device. Field-installable bolt-on TXVs 

are also available. Primary & secondary condensate drain. All drain 

connections are 3/4” MPT. Access door allows for coil cleaning. Cer-

tified for use with either R22 or R410a.

VII. Warranty

One year limited parts warranty.

Summary of Contents for GAS Series

Page 1: ...r service personnel CAUTION CAUTION WARNING WARNING WARNING WARNING WARNING WARNING GAT GAS Series Horizontal Ceiling Mount Electric Heat Dx Cool Air Handler 2 Introduction The GAT GAS Series air hand...

Page 2: ...vel All main supply and return air drops should be properly size as deter mined by the designer of the duct system and should not necessarily be the size of the duct flange openings of the unit The dr...

Page 3: ...burr free and clean Failure to do so may increase chances of a leak It is recommended to use a pipe cutter to remove the spun closed end of the suction line To reduce air leakage rubber gommets may b...

Page 4: ...nstructions are separated into sec tions by metering device 2 A ducted return requires a non louvered panel 1 A bottom return installation requires a louvered panel 3 Both louvered and non louvered pa...

Page 5: ...eflon O ring is located between the two halves of the flowrator CAUTION I 2 Replace the Teflon O ring located between the halves Discard Schrader if present During some installations a piston change m...

Page 6: ...to install the right valve can lead to poor per formance and possible compressor damage CAUTION Ensure that the TXV bulb is in direct con tact with the suction vapor line Gap be tween the bulb and tub...

Page 7: ...to the liquid line stub out See 8A I 3 Do not attempt to touch brazed joints while hot Severe burns may result WARNING III 3 After ensuring that the Teflon O ring seal is still in place inside the flo...

Page 8: ...connections using proper brazing pro cedures 9 When all line connections are brazed perform a proper system evacuation procedure per the outdoor unit manufacturer instructions 10 Seal the penetration...

Page 9: ...t 42 61 S Small Cabinet 18 36 Heat Strip 00 NO Heat BLOWER DATA UNIT MODEL RPM AMP VOLT HP CFM VS STATIC PRESSURE 0 00 0 10 0 20 0 30 0 40 GAT 18 1625 1 4 240 1 4 850 775 700 675 600 GAT 24 1000 900 8...

Page 10: ...ssure measuring device 0 1 0 in slope gauge and a tempera ture measuring device 0 200 F thermometer 3 Release system charge from outdoor unit and call for cooling 4 Use outdoor unit equipment manufact...

Page 11: ...are so that you may cut off the flow of energy in the event of overheating WARNING optimum equipment efficiency and performance Inspect and clean or replace filters every month This routine maintenanc...

Page 12: ...MER 24 VOLTS HTR 3 BK CB CB LC LC HS LO SPEED CAPPED MED SPEED CAPPED HS HS BLOWER MOTOR SPEED SETTING FOR MAX KW RATING UNIT MODEL MAX KW SPEED TAP ELECTRIC HEAT ONLY ELECTRIC HEAT HEAT PUMP MAX KW S...

Page 13: ...IO 123114 Effective 12 04 2014 13...