5
1.2.
Transport of semicompact units
Semicompact units consist of two or three blocks that form the unit once they are connected together.
Lift the blocks of semicompact units one after another.
Tie up individual blocks from underneath before lifting them.
2 .
E q u i p m e n t i n s t a l l a t i o n
2.1.
Safety rules
●
The equipment in the indoor version is designed for basic environment - environmental
temperature must be b5°C to +55°C
,
relative humidity 60
% (60%
relative humidity up to
20°C). If an equipment is placed in another location it is necessary to ensure the adequate
protection.
●
The source of warm water has to be permanently connected to the device, so the constant intake
of warm water is ensured.
●
Protect the unit from freezing internal components during periods of inactivity to ensure
mechanical backflow valve in the pipe i2.
●
The appliance may be operated within the temperature range of ventilation air between -25°C and
+40°C with relative exhaust air humidity up to 80%, in an environment where there is no risk of fire
or an explosion of flammable gases and fumes, and air transported must not contain organic
solvents or aggressive substances that might damage mechanical parts of the unit. If there is a
danger of such gases and fumes temporarily entering the duct system (e.g. during floor bonding,
painting), the unit must be switched off sufficiently in advance.
●
Be careful during the installation not to damage the unit casing (e.g. by hanging it only on two
suspension brackets).
●
After placing the equipment make sure its position is stable and secure the equipment against
possible movement.
●
Follow all work safety rules during the manipulation and installation work (including the work safety
for work in heights and lifting weights) and use proper tools and protective clothing.
●
Only a qualified person may operate the lifting equipment and binding tools.
Appliances with hot water heaters
●
Must be permanently connected to power supply to provide for the anti-freeze protection of the hot
water heater. In the case of a prolonged power outage the heating medium must be drained from
the hot water heater including the control set. We recommend draining water from the heater with
pressurized air, not using a gravity flow!
●
It may only be operated if the heating system including the hot water heater and control set are
filled with a heating medium and air bled; also applies to periods outside the heating season! In
case the heating system including the hot water heater and control set are not filled with a heating
Blocks of semicompact unit
The lifting bars must be
wider than the lifted unit.