medium, the appliance must be drained of the remaining heating medium, dried properly and
disconnected from power supply.

2.2.

Hygienic instructions and requirements

If installation is interrupted or heavy dusting occurs, cover all openings of the appliance in such a

 

way so as to ensure that surfaces to be in contact with transported air remain protected against

 

the 

weather and stay clean and dry.

If long-term high relative humidity (short-term more than 90 % or more than 80 % for three

 

consecutive days) is likely to occur with the subsequent moistening of filters (e.g. in areas with

 

frequent fogs, frequent and long rains, flying snow etc.), suitable measures must be taken to

 

prevent microbiologic growth. Recommended measures include more frequent hygienic checks as

 

per VDI 6022 or shorter filter replacement intervals. Another option is the preheating of air using

 

an 

appropriate control devices (electrical duct heaters are an available accessory), or the

 

appliance 

must be put out of operation for the period when filters are at the risk of moistening (if

 

the type of 

operation allows this).

Should such weather conditions occur at the site of installation that would cause the dew point to

 

be 

exceeded in the supply air region of the heat recovery exchanger, or an independent cooling

 

system is installed in ventilated rooms, 

Duplexvent

 units may only be used provided that it has been

 

arranged via appropriate measures that the dew point is not exceeded in the heat recovery

 

exchanger. The typical weather of central Europe makes this condition almost impossible.

The e1/ODA air supply chamber has no water drain. An accessible and cleanable chamber with a

 

drain of precipitated water must be installed upstream the outdoor air inlet into the appliance.

The HVAC network of appliances operated in an environment with Class ETA 2 extract air must

 

be 

arranged for operation in such a way so that positive pressure is on the supply air side of the

 

heat 

recovery unit; in an environment with Class ETA 3 extract air must be arranged for operation

 

in 

such a way so that positive pressure is on the supply side in comparison to the exhaust side.

 

This 

must be ensured under all operating conditions of the system. For more details see EN

 

13779.

Unpack and install air filters in the last step, just before putting the appliance into operation. You

 

will 

prevent the filters from getting dirty.

Air duct including accessories with autonomous regulation of operation is to be connected on the

 

fresh air supply. Such duct will, in compliance with the regulation VDI 6022, provide for

 

appropriate 

treatment of supplied fresh air to prevent air filter from getting wet. In case the duct is

 

not connected 

or if it does not include such accessory, the appliance is to be put out of operation

 

as long as the 

risk of air filters to get wet persists (thick fog, snowing).

Ü

In compliance with hygienic standard VDI 6022 HVAC systems must be equipped with shut-off

 

dampers to ensure the automatic closure of the system so that no air can flow freely through the

 

system. We recommend using shut-off dampers available as an accessory. It is the responsibility

 

of 

the planner / specialist installation firm to comply with this requirement.

Ü

Duplexvent

 series appliances have a single-stage filtration system. Appliances in a hygienic version

 

in compliance with hygienic standard VDI 6022 must have a Class F7 / ePM1 50% filter fitted on

 

the inlet; applies to outdoor air (e1/ODA) class ODA 1 and ODA 2. When outdoor air is Class 3, an

 

M5 / ePM10 50% / ePM10 50% Class filter must be fitted in the duct upstream the outdoor air inlet

 

into the HVAC unit; alternatively, an M5 / ePM10 50% Class filter may be installed in the HVAC

 

unit 

and an F7 / ePM1 50% Class filter in the duct at the e2/SUP outlet from the unit. Note: M5 /ePM10 
50% and F7 / ePM1 55% filters are separately supplied accessories.

Ü

Appliances in a hygienic version in compliance with hygienic standard VDI 6022 may be operated

 

only if the use of recirculating air is suitable for hygienic reasons or the arrangement of operation

 

of 

the HVAC network ensures positive pressure in the supply section of the appliance against the

 

extraction section.

Summary of Contents for Duplexvent MULTI

Page 1: ...INSTRUCTION MANUAL for Duplexvent MULTI MULTI ECO and Basic units indoor version...

Page 2: ...ufacturer s technical conditions and respective valid regulations and technical standards The equipment must not be installed and operated in aggressive environment which could damage inner and outer...

Page 3: ...ns 21 2 9 Condensate drain connection 21 2 10 Connecting hot water heating coil to a heating water supply 22 2 11 Connecting chilled water cooling coil to a chilled water supply 22 2 12 Connecting dir...

Page 4: ...water during transportation and prior to completing the appliance assembly All holes must be covered with protective lids The same applies when the appliance is transported disassembled Secure the equ...

Page 5: ...ere is a danger of such gases and fumes temporarily entering the duct system e g during floor bonding painting the unit must be switched off sufficiently in advance Be careful during the installation...

Page 6: ...ronment with Class ETA 3 extract air must be arranged for operation in such a way so that positive pressure is on the supply side in comparison to the exhaust side This must be ensured under all opera...

Page 7: ...exchanger 5 Water cooling direct evaporator 6 Water heating 7 Supply fan 8 Exhaust supply air 9 Intake supply air 10 Supply air filter 11 Bypass flap 12 Condensate drain 13 Circulation flap 14 Exhaus...

Page 8: ...ation units are depicted in Duplexvent selection SW when you select the Duplexvent unit Design Show total dimensions The information is available also in technical datasheets as well as in the technic...

Page 9: ...0 700 7100 Basic 1300 900 8100 Basic 1300 1100 10100 Basic 1500 1300 Floor standing position The appliance is placed on a base frame which is attached on the bottom side of the unit It is not allowed...

Page 10: ...ter side of the casing horizontally The unit must be secured against movement Ceiling suspended position Slope both the longer and shorter side of the casing 3 towards the condensate drain at exhaust...

Page 11: ...ct on the ventilation unit Below you will find examples of unit suspension 500 1000 Multi 500 1100 MultiEco 1500 6500 Multi 1500 5500 MultiEco Description Description 1 Screw rod M10 1 Screw rod M10 2...

Page 12: ...xvent 12100 15100 Basic are a new generation of versatile outdoor ventilation units with counterflow Multi Multi Eco and crossflow Basic heat recovery exchangers The units consist of two or three bloc...

Page 13: ...escribed in the Chapter 7 Assembly of blocks Make sure that the surface of the intended placement of the unit is even Mount adjustable bases part of delivery on all stand feet Screw the adjustable bas...

Page 14: ...ll around the bottom inlet of the block Place the blocks next to each other and make sure they are all levelled Adjust the stand feet as needed Using the spirit level make sure that the blocks 1 2 and...

Page 15: ...2 by using M8 bolts slightly together Use triangle members in inner corners Slightly tighten the upper part of blocks 1 and 2 using M8 bolts and nuts x y z 1 2 3 Levelling the blocks of the unit 1 2 3...

Page 16: ...act air 2 Exhaust fan Mi 3 Temperature sensor TU2 4 Manometer of exhaust fan PMi 5 Heat exchanger 6 Water cooling direct evaporator 7 Water heating 8 Capillary thermostat TFK 9 Manometer of supply fan...

Page 17: ...e cable Mi with the working voltage 400V from the junction box into the wiring box Connect the blocks 1 with 2 and subsequently 2 with 3 by green yellow grounding wires cable comes connected on delive...

Page 18: ...ox Manostat PFe is connected to the wiring box Connected on delivery optional equipment Manometer cable PMe is connected to the junction box Pressure measurement point PDi measuring the pressure incre...

Page 19: ...g box Connected on delivery optional equipment The circuit of cooler CHW is connected to the hydraulic kit The circuit of heater TPO is connected to the hydraulic kit Hydraulic kit LS controlling the...

Page 20: ...the slots Cover the slots where cables lead from the junction box Use cover metal sheets and 4mm rivets supplied along with the unit Cover the connected junction box In case the wires of unit blocks a...

Page 21: ...as in the picture below Sufficiently fix the trap s shape 2 Connect a pipe of the same or larger diameter to each trap and connect the pipes to a sewer 3 Make sure the whole pipe run including inside...

Page 22: ...en a 3 way mixing manifold is used we recommend installing a short circuit by pass Fluid pre heater power control 1 The pre heater is used for protecting heat recovery exchangers from freezing 2 The R...

Page 23: ...h air filter Make sure that the location of the label enables regular inspection of values to be measured 3 Fully unscrew the rotation knob for setting zero on the scale bottom knob marked and then sc...

Page 24: ...d on separate documentation 5 You will find the description of the control in a separate documentation called Regulation control The unit shall be protected using a breaker with characteristics C In c...

Page 25: ...og 5 Access to the unit using the internet Ventilation units Multi MultiEco and Basic equipped with control system RD5 1 can also be controlled using a web browser This allows the user to do the follo...

Page 26: ...d up to the junction box Fan Mi is connected to the connector Connect Connect grey connector above the middle block Unit with RD5 CPM regulation2 Unit without regulation Connect the blocks 1 with 2 an...

Page 27: ...x Cable powering the condensate heating HC is connected to the connector Connect Lead the cables TEA and TU2 with temperature sensors from the junction box into their intended position Connect optiona...

Page 28: ...essure measurement point are installed Connect optional equipment Connect grey connector which powers manostat PFe The same connector powers also the servo drive of the flap Se Unit with RD5 CPM regul...

Page 29: ...lic kit Hydraulic kit LS controlling the chiller or heater is located on the upper side of the unit The kit is completely connected up to the junction box Water pump LP in the heating circuit is locat...

Page 30: ...by RD5 regulation or for units without regulation Connect connector powering the supply air flap Se the same connector powers also the manostat PFe Unit with RD5 CPM control system Unit without contr...

Page 31: ...31 Notes...

Page 32: ...80000582 Issue 2 01 21 Call 01494 525252...

Reviews: