23
2.14.
Installation and connection of inclined manometers
If the appliance is supplied without liquid manometers for measuring the pressure difference of air
filters, place each manometer on a suitable vertical surface near the pressure measurement points
(the maximum length of connecting hoses is 1 meter). Suitable location is indicated in the production
by a sunk slot where drilling can begin. Make sure that the location of manometers enables regular
inspection of values to be measured. Adjust manometers in horizontal position and secure them with
self-tapping screws provided.
1.
Connect monometers using hoses with the pressure measurement points on the casing of the
appliance. Connect the hose on the top of the manometer and lead it to the plastic bushing on the
casing of the appliance. The hose must always connect two identical connecting points marked
with "+" or "-" (may not be combined). Make sure that hoses from only one filter are connected to
each single manometer!
2.
Stick a relevant label supplied together with accompanying documentation near each manometer.
The label contains information about each air filter. Make sure that the location of the label
enables regular inspection of values to be measured.
3.
Fully unscrew the rotation knob for setting zero on the scale (bottom knob marked "+") and then
screw it approximately two full turns back to allow for setting in both directions.
4.
Unscrew the “FILL” plug (top knob) and start filling the appliance with measurement fluid (part of
delivery) until you can see the fluid near zero on the scale. Use the bottom knob to accurately set
the zero value on the scale. Screw the top filling plug back.
After connecting manometers do not tilt the appliance or door if manometers are located there!
Danger of measurement fluid leakage.
2.15.
Fitting air filters
1.
If the appliance was supplied with separately packed filter cartridges, unpack the cartridges and
check their condition. If they are damaged or stained, replace them. Spare filter cartridges may be
ordered from the manufacturer. Please include in the order the ordering number of the cartridge (the
number is shown on the identification plate).
2.
Insert undamaged and clean cartridges into the guides. To access filter in a semicompact unit open
or pull away the door behind which the filter is located.
Installation of manometers (floor standing flat unit):
Fitting filter in
semicompact unit
Fitting filter in
compact unit