Notes:
TCF24X22G-27
TCF24X24G-27
SEPR
1,3,5
8.1
8.2
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
827901.7
865343.5
Rated Refrigerant Capacity P
A
1,3,5
kW
905.3
954.9
Rated Power Input D
A
kW
281.6
296.8
Rated EER
DC,A
3.22
3.22
Declared Refrigerant Capacity P
B
1,3,5
kW
844.7
890.9
Declared Power Input D
B
kW
186.8
194.9
Declared EER
DC,B
4.52
4.57
Declared Refrigerant Capacity P
C
1,3,5
kW
784.0
826.9
Declared Power Input D
C
kW
120.8
126.3
Declared EER
DC,C
6.49
6.55
Declared Refrigerant Capacity P
D
1,3,5
kW
723.3
762.9
Declared Power Input D
D
kW
51.4
53.7
Declared EER
DC,D
14.08
14.21
SSCEE
2,3,5
%
199.5
199.4
SSCEE Tier
Tier 2 (2021)
Tier 2 (2021)
Rated Cooling Capacity P
rated,c
2,4,5
kW
910.0
960.0
Declared Cooling Capacity 35°C Pdc 2,3,5
kW
905.3
954.9
Declared EER
d
35°C
3.22
3.22
Declared Cooling Capacity 30°C Pdc 2,3,5
kW
665.9
702.2
Declared EER
d
30°C
4.26
4.26
Declared Cooling Capacity 25°C Pdc 2,3,5
kW
426.4
449.6
Declared EER
d
25°C
6.05
6.09
Declared Cooling Capacity 20°C Pdc 2,3,5
kW
186.9
197.0
Declared EER
d
20°C
6.03
5.99
Sound Power Level
dB(A)
93
93
Air Volume
m³/h
454577
495902
Off mode P
OFF
kW
0.427
0.427
Thermostat-off mode P
TO
kW
4.650
5.140
Standby Mode P
SB
kW
0.749
0.759
Crankcase heater mode P
CK
kW
0.000
0.000
Technical Data
Ecodesign
TCF24X22G-27, TCF24X24G-27
Introduction
Chillers
TurboChill™ R1234ze Air Cooled and FreeCool
194
Chiller Technical Manual 7752785 V1.12.0_10_2018
Te
ch
ni
ca
l
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside configuration.