TurboChill™ R1234ze Air Cooled and FreeCool
99
Chiller Technical Manual 7752785 V1.12.0_10_2018
Fre
eC
oo
l
TCF22X10G-22, TCF22X12G-22, TCF22X14G-22
Technical Data
Electrical Data
Electrical Data
Units
TCF22X10G-22
TCF22X12G-22
TCF22X14G-22
Unit Data
Full Load Amps (1)
A
339
347
355
Maximum Start Amps
A
189
197
205
Mains Supply
VAC
400V (±10%) 3PH 50Hz
Recommended Mains Fuse Size
A
355
355
355
Max Mains Incoming Cable Size (Direct
to 3 Phase Mains Isolator)
mm²
2x 300mm² (Torque >20Nm)
Independent Permanent Supply
Recommended Fuse Size
A
25
25
25
Independent Permanent Supply
VAC
230V 1PH 50Hz (±10%)
Max Permanent Incoming Cable Size
(Direct to Control Panel Isolator)
mm²
6mm² / 8 AWG
Control Circuit
VAC
24 VAC & 230VAC (±10%)
Evaporator
Immersion Heater Rating
W
340 (2x 170)
340 (2x 170)
340 (2x 170)
External Trace Heating
Available (fitted by others)
W
500
500
500
Condenser Fan - Per Fan (EC)
Quantity
10
12
14
Full Load Amps
A
3.9
3.9
3.9
Locked Rotor Amps
A
N/A
N/A
N/A
Motor Rating
kW
2.56
2.56
2.56
Compressor - Per Compressor
Nominal Run Amps
A
150
150
150
Quantity
1 / 1
1 / 1
1 / 1
Motor Rating
kW
92
92
92
Start Amps
A
2
2
2
Type Of Start
Electronic Soft Start
(1) Based at full load Conditions and EC Fans
Pump electrical data is available from Airedale upon request.