Notes:
TCC11X04G-01
TCC11X06G-01
TCC11X08G-01
SEPR
1,3,5
8.0
8.8
9.2
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
186386.5
190217.3
201921.2
Rated Refrigerant Capacity P
A
1,3,5
kW
199.4
224.3
249.1
Rated Power Input D
A
kW
59.7
57.4
61.0
Rated EER
DC,A
3.34
3.91
4.08
Declared Refrigerant Capacity P
B
1,3,5
kW
186.1
209.3
232.4
Declared Power Input D
B
kW
37.4
38.1
40.4
Declared EER
DC,B
4.98
5.49
5.75
Declared Refrigerant Capacity P
C
1,3,5
kW
172.7
194.3
215.8
Declared Power Input D
C
kW
23.8
24.3
25.8
Declared EER
DC,C
7.26
7.99
8.35
Declared Refrigerant Capacity P
D
1,3,5
kW
159.4
179.3
199.1
Declared Power Input D
D
kW
14.6
14.9
15.8
Declared EER
DC,D
10.91
12.01
12.58
SSCEE
2,3,5
%
193.4
226.8
231.5
SSCEE Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Rated Cooling Capacity P
rated,c
2,4,5
kW
200.0
225.0
250.0
Declared Cooling Capacity 35°C Pdc 2,3,5
kW
199.4
224.3
249.1
Declared EER
d
35°C
3.34
3.91
4.08
Declared Cooling Capacity 30°C Pdc 2,3,5
kW
146.8
165.1
183.3
Declared EER
d
30°C
4.30
4.85
5.13
Declared Cooling Capacity 25°C Pdc 2,3,5
kW
111.5
105.8
114.6
Declared EER
d
25°C
5.01
6.44
6.30
Declared Cooling Capacity 20°C Pdc 2,3,5
kW
98.1
95.0
93.2
Declared EER
d
20°C
6.76
7.36
7.66
Sound Power Level
dB(A)
87
87
87
Air Volume
m³/h
82650
123975
165301
Off mode P
OFF
kW
0.249
0.249
0.249
Thermostat-off mode P
TO
kW
0.594
0.738
0.897
Standby Mode P
SB
kW
0.330
0.340
0.350
Crankcase heater mode P
CK
kW
0.000
0.000
0.000
Technical Data - TCC X
Ecodesign
TCC11X04G-01, TCC11X06G-01, TCC11X08G-01
Introduction
Chillers
TurboChill™ R1234ze Air Cooled and FreeCool
171
Chiller Technical Manual 7752785 V1.12.0_10_2018
Te
ch
nic
al
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside configuration.