Liquid Level Sensor
The liquid level sensor is designed to measure the amount of refrigerant inside the flooded evaporator of a Turbochill
and send a current signal between 4 and 20mA to the microprocessor.
This signal is used by the controller to control the flow of refrigerant into the evaporator for optimal and energy efficient
performance. The liquid level sensor will be calibrated and located on the evaporator upon dispatch of the unit. However
in the following section there is a quick guide on how to reset and recalibrate the sensor.
Step 1
Connect the USB cable (HBxC-
USB) to the laptop. Connect the
cable to the sensor. Open the HBLC
Tool software
Step 2
Once the following dialog is open,
press “Start Scan for Sensor”
Step 3
Once detected then the tool shown
in Figure 3 will open. Change all
parameters as per Figure 3 ensuring
all avalible boxes are ticked
Step 4
Press the “Advanced Settings” tab,
all setting stay the same as upon
arrival.
Step 5
Click the “Save to sensor” button
shown in Figure 4.
Once the upload is complete Figure
5 will be shown and the program
can be closed.