Technical Data
Ecodesign
Notes:
TCC22X14G-14
TCC23X12G-17
TCC23X14G-17
SEPR
1,3,5
8.6
7.8
8.0
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
448182.6
561629.2
590340.9
Rated Refrigerant Capacity P
A
1,3,5
kW
518.4
588.9
638.6
Rated Power Input D
A
kW
135.1
174.6
179.7
Rated EER
DC,A
3.84
3.37
3.55
Declared Refrigerant Capacity P
B
1,3,5
kW
483.8
549.5
596.0
Declared Power Input D
B
kW
88.8
113.8
118.7
Declared EER
DC,B
5.45
4.83
5.02
Declared Refrigerant Capacity P
C
1,3,5
kW
449.1
510.2
553.3
Declared Power Input D
C
kW
57.2
72.0
75.7
Declared EER
DC,C
7.85
7.08
7.31
Declared Refrigerant Capacity P
D
1,3,5
kW
414.4
470.9
510.6
Declared Power Input D
D
kW
35.5
43.8
46.3
Declared EER
DC,D
11.69
10.75
11.03
SSCEE
2,3,5
%
215.5
224.8
231.4
SSCEE Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Rated Cooling Capacity P
rated,c
2,4,5
kW
520.0
590.0
640.0
Declared Cooling Capacity 35°C Pdc 2,3,5
kW
518.4
588.9
638.6
Declared EER
d
35°C
3.84
3.37
3.55
Declared Cooling Capacity 30°C Pdc 2,3,5
kW
381.6
433.6
470.2
Declared EER
d
30°C
4.91
4.59
4.78
Declared Cooling Capacity 25°C Pdc 2,3,5
kW
244.8
278.4
301.8
Declared EER
d
25°C
5.85
6.01
6.16
Declared Cooling Capacity 20°C Pdc 2,3,5
kW
108.0
123.1
133.4
Declared EER
d
20°C
6.67
8.27
8.39
Sound Power Level
dB(A)
90
92
92
Air Volume
m³/h
289276
247951
289276
Off mode P
OFF
kW
0.322
0.375
0.375
Thermostat-off mode P
TO
kW
1.555
1.119
1.353
Standby Mode P
SB
kW
0.504
0.596
0.606
Crankcase heater mode P
CK
kW
0.000
0.000
0.000
TCC22X14G-14, TCC23X12G-17, TCC23X14G-17
Introduction
Chillers
TurboChill™ R1234ze Air Cooled and FreeCool
175
Chiller Technical Manual 7752785 V1.12.0_10_2018
Te
ch
nic
al
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside configuration.