Notes:
TCC22R14G-14
TCC23R12G-17
TCC23R14G-17
SEPR
1,3,5
8.2
7.5
7.7
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
509024.7
623319.1
655029.0
Rated Refrigerant Capacity P
A
1,3,5
kW
558.2
628.7
678.4
Rated Power Input D
A
kW
152.7
185.1
195.1
Rated EER
DC,A
3.66
3.40
3.48
Declared Refrigerant Capacity P
B
1,3,5
kW
520.8
586.7
633.1
Declared Power Input D
B
kW
99.8
124.5
130.6
Declared EER
DC,B
5.22
4.71
4.85
Declared Refrigerant Capacity P
C
1,3,5
kW
483.5
544.7
587.8
Declared Power Input D
C
kW
65.1
79.8
83.9
Declared EER
DC,C
7.42
6.83
7.01
Declared Refrigerant Capacity P
D
1,3,5
kW
446.2
502.7
542.4
Declared Power Input D
D
kW
40.4
49.2
51.7
Declared EER
DC,D
11.05
10.22
10.50
SSCEE
2,3,5
%
218.7
221.2
226.4
SSCEE Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Rated Cooling Capacity P
rated,c
2,4,5
kW
560.0
630.0
680.0
Declared Cooling Capacity 35°C Pdc 2,3,5
kW
558.2
628.7
678.4
Declared EER
d
35°C
3.66
3.40
3.48
Declared Cooling Capacity 30°C Pdc 2,3,5
kW
410.8
462.9
499.5
Declared EER
d
30°C
4.81
4.53
4.64
Declared Cooling Capacity 25°C Pdc 2,3,5
kW
263.4
297.1
320.5
Declared EER
d
25°C
6.15
5.89
6.07
Declared Cooling Capacity 20°C Pdc 2,3,5
kW
123.2
131.3
141.6
Declared EER
d
20°C
6.83
8.10
8.20
Sound Power Level
dB(A)
90
92
92
Air Volume
m³/h
289276
247951
289276
Off mode P
OFF
kW
0.322
0.375
0.375
Thermostat-off mode P
TO
kW
1.844
1.304
1.560
Standby Mode P
SB
kW
0.504
0.596
0.606
Crankcase heater mode P
CK
kW
0.000
0.000
0.000
Technical Data
Ecodesign
TCC22R14G-14, TCC23R12G-17, TCC23R14G-17
Introduction
Chillers
TurboChill™ R1234ze Air Cooled and FreeCool
167
Chiller Technical Manual 7752785 V1.12.0_10_2018
Te
ch
nic
al
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside configuration.