Chillers
TurboChill™ R1234ze Air Cooled and FreeCool
135
Chiller Technical Manual 7752785 V1.12.0_10_2018
Installation Data
Anti Vibration Mounting (Optional)
Spring Type
Each mount is coloured to indicate the different loads, refer to instructions supplied for
correct allocation.
Dimensions
A(1)
B
C
D
E
F
TCC / TCF Units
162
130 225 186 20
16
(1)
Unloaded dimension
Components
1
Locating Screw
2
Retaining Nut & Washer
3
Levelling Screw
4
Levelling Lock Nut
5
Retaining Studs
6a
Upper Retaining Nuts
6b
Lower Retaining Nuts
7
Spring Assembly
8
Pressure Plate
9
Top Plate
10
Bolting-down Holes
Installation
1. Locate and secure mount using bolting down holes (10) in base plate.
2. Ensure mounts are located in line with the unit base.
3.
If applicable, remove compressor enclosure covers to allow access to mount fixing
holes in the unit base.
4. Lock the upper retaining nuts (6a) to the underside of the top plate (9) before a load is
applied.
5. Slacken levelling lock nut (4). (the levelling screw will not move if this is not slackened)
6. Remove retaining nut and washer (2), lower the unit onto the mounts and replace
retaining nut and washer.
Beginning with the mount with the largest deflection adjust the height of each mount using
the levelling screw (3).
Mountings must be adjusted incrementally in turn. Do not fully adjust 1 mount at a time as
this may overload and damage springs.
WHEN ALL MOUNTS ARE LEVEL, LOCK EACH INTO PLACE USING THE LEVELLING LOCK NUT (4)
7. Lock all retaining nuts (6a and 6b) to the extreme ends of the retaining studs (5)
Do not connect any services until all anti vibration mounts have been fully adjusted.
Pad Type
Components/Installation
1. M16 Bolt (Not Supplied)
2. Washer (Not Supplied)
3. Fixing Pad 6173231
4. AV Pad 6173223
5. 2 x M16 Nut (Not Supplied)
6. Unit Base
7. Unit Mounting Plinth
2
1
6a
5
6b
10
9
8
7
3 4
B
A
C
D
E
F
E
1
2
3
2
5
4
3
6
7