Top menu
Level
Pgm No.
Submenu 1
Submenu 2
Default
Setting
Heating
circuit 1
Eu
710
Ҙ
Room comfort setpoint
20.0°C
Eu
712
Ҙ
Room reduced setpoint
16.0°C
Eu
714
Ҙ
Room frost protection
setpoint
10.0°C
E
716
Ҙ
Comfort setpoint max
35.0°C
Eu
720
Ҙ
Heating curve slope
1.5
E
721
Ҙ
Heating curve displacement
0.0°C
E
726
Ҙ
Heating curve adaptation
Off
On
Off
Eu
730
Ҙ
Summer/winter heating limit
18.0°C
E
732
Ҙ
24-hour heating limit
-3°C
E
733
Ҙ
Ext’n 24-hour heating limit
No
Yes
Yes
C
740
Ҙ
Flow temp setpoint min
8°C
C
741
Ҙ
Flow temp setpoint max
90°C
Eu
742
Ҙ
Flow temp setpoint room
stat
65°C
E
744
Ҙ
Swi-on ratio room stat
---
C
746
Ҙ
Delay heat request
0 s
E
750
Ҙ
Room influence
20%
E
760
Ҙ
Room temp limitation
1°C
E
770
Ҙ
Boost heating
3°C
E
780
Ҙ
Quick setback
Off
To reduced setpoint
To frost prot setpoint
Off
E
790
Ҙ
Optimum start control max
0 min
E
791
Ҙ
Optimum stop control max
0 min
E
800
Ҙ
Reduced setp increase start
-5°C
E
801
Ҙ
Reduced setp increase end
-15°C
E
809
Ҙ
Continuous pump operation
No
Yes
No
E
820
Ҙ
Overtemp prot pump circuit
Off
On
On
E
830
Ҙ
Mixing valve boost
5°C
E
832
Ҙ
Actuator type
2 position
3 position
3 position
E
833
Ҙ
Switching differential 2-pos
2°C
E
834
Ҙ
Actuator running time
120 s
C
850
Ҙ
Floor curing function
Off
Functional heating
Curing heating
Curing/Functional
heating
Functional/Curing
heating
Manually
Off
C
851
Ҙ
Floor curing setp manually
25°C
Eu
855
Ҙ
Floor curing setp current /
Floor curing day current