![AIC N 100 WH Installation And Maintenance Manual Download Page 14](http://html1.mh-extra.com/html/aic/n-100-wh/n-100-wh_installation-and-maintenance-manual_2870754014.webp)
G-14
Z-038791_EN • Rev A
T
echnical
S
pecificaTionS
Performance and Efficiency Data
N 60 WH
(min. - max.)
N 80 WH
(min. - max.)
N 100 WH
(min. - max.)
N 120 WH
(min. - max.)
heat input (net)
kW
8.2 - 60.0
8.2 - 80.0
12.0 - 100.0
12.0 - 120.0
heat output at 80/60°C
kW
8.0- 58.3
8.0 - 77,7
11.8 - 97.6
11.8 - 117.1
heat output at 50/30°C
kW
8.8 - 63.3
8.8 - 84.4
12.9 - 106.2
12.9 - 127.4
heating efficiency 80/60°C
%
97.8 - 97.1
97.8 - 97.1
98.0 - 97.6
98.0 - 97.6
heating efficiency 50/30°C
%
107.9 - 105.5
107.9 - 105.5
107.8 - 106.2
107.8 - 106.2
useful efficiency at 30%
(return at 30°C)
%
108.4
108.3
108.3
108.2
seasonal efficiency
%
93.0
93.0
93.0
93.0
boiler type and model
N 60 WH
N 80 WH
N 100 WH
N 120 WH
condensing boiler
Y/N
Y
Y
Y
Y
low temp boiler
Y/N
Y
Y
Y
Y
combination heater
Y/N
N
N
N
N
useful heat output
at 30% of rated heat output (
P
1
)
kW
19.5
26.0
32.6
39.1
at rated output and high-temp
regime (
P
4
)
kW
58.3
77.8
97.5
117.1
useful efficiency
at 30% of rated heat output (
η
1
)
%
97.6
97.6
97.4
97.5
at rated output and high-temp
regime (
η
4
)
%
87.9
88.1
88.3
88.4
auxiliary electricity consumption
at full load (
elmax
)
kW
0.10
0.15
0.24
0.30
at part load (
elmin
)
kW
0.028
0.042
0.060
0.070
in standby mode (
P
SB
)
kW
0.003
0.003
0.003
0.003
standby heat loss (
P
stby
)
kW
0.07
0.07
0.12
0.12
annual energy consumption for
space heating
kWh
34,530
―
―
―
sound power level indoors LWA
dB
58
―
―
―
* calculated for G20 gas type
ERP Data