![AIC N 100 WH Installation And Maintenance Manual Download Page 15](http://html1.mh-extra.com/html/aic/n-100-wh/n-100-wh_installation-and-maintenance-manual_2870754015.webp)
G-15
Z-038791_EN • Rev A
T
echnical
S
pecificaTionS
Electrical Data
N 60 WH
N 80 WH
N 100 WH
N 120 WH
supply voltage / frequency /
current
V / Hz / A
230 / 50 / 6
protection class
IP
X4D
Combustion and Gas Data
N 60 WH
(min. - max.)
N 80 WH
(min. - max.)
N 100 WH
(min. - max.)
N 120 WH
(min. - max.)
chimney type(s)
B
23
, B
23P
, C
13(x)
, C
33(x)
, C
43(x)
, C
53(x)
, C
63(x)
, C
83(x)
, C
93(x)
flue gas temperature at 80/60°C
°C
60.0 - 76.5
60.0 - 82.6
60.0 - 75.3
60.0 - 79.1
flue gas temperature at 50/30°C
°C
30.0 - 52.1
30.0 - 51.3
30.0 - 50.6
30.0 - 50.1
overheat flue gas temperature
°C
110
max. flue gas pressure
(incl. max wind condition)
Pa
200
230
250
300
Max. chimney length (100/150)
m
25
mass flow rate of flue gases
g/s
3.5 - 26.0
3.5 - 35.3
5.1 - 43.5
5.3 - 51.8
max. condensate volume
kg/h
7.6
10.2
12.7
15.3
CO emissions
mg/kWh
64.8
32.0
80.2
69.7
CO
2
contents (G20) (± 0.1)
%
8.3 - 8.6
8.3 - 8.6
8.3 - 8.7
8.3 - 8.7
CO
2
contents (G25) (± 0.2)
%
8.5 - 9.0
CO
2
contents (G31) (± 0.2)
%
10.0 - 10.5
NOx level (weighted)
mg/kWh
32.6
32.1
39.8
37.0
NOx class
6
gas type(s)
G20 - G25 - G25.3 - G31
gas categories
I2E(S), II2E3P, II2Er3P, II2H3P, II2EK3P, I2ELL, I3P
gas pressure
G20 (20 mbar)
mbar
17 - 25
G25 (25 mbar)
mbar
20 - 30
G25.3 (25 mbar)
mbar
18 - 33
G31 (30/37/50 mbar)
mbar
25.0-35.0 / 25.0-45.0 / 42.5-57.5
gas flow rate (G20)*
m
3
/h
0.85 - 6.36
0.84 - 8.44
1.22 - 10.39
1.28 - 12.40
gas flow rate (G25)*
m
3
/h
0.95 - 7.03
0.94 - 9.45
1.38 - 11.86
3.19 - 13.90
gas flow rate (G31)*
m
3
/h
0.35 - 2.47
0.40 - 3.22
5.15 - 4.09
0.50 - 4.83
*
15°C, 1013.25 mbar, dry gas