Agilent Technologies 1989–2002
Agilent 3070 / 79000 Site Preparation
6-7
Chapter 6: Site Preparation – Power Requirements: Power Requirements
Table 6-1
Series 3 and 79000 power requirements
PDU
Power
Option
Voltage
line-to-neut
/ line-to-line
Full-Load Amps (FLA) for:
327X
79000
317X
307X
xDSL/POTS Bay
200–240V 3-Phase Delta
3PD
200
220
230
240
13
13
13
13
14
14
14
14
18
18
18
18
24
24
24
24
12
12
12
12
208–220V 3-Phase Wyel
3PY
120 / 208
127 / 220
13
13
14
14
18
18
24
24
12
12
380–415V 3-Phase Wye w/Neutral
3PN
220 / 380
230 / 400
240 / 415
9
9
9
10
10
10
10
10
10
16
16
16
10
10
10
L1
L3
L2
G
L1
L3
L2
G
L1
L3
L2
N
G