Agilent Technologies 1989–2002
Agilent 3070 / 79000 Site Preparation
11-7
Chapter 11: Site Preparation – Series 3 / 79000 Current Reduction Conversion: Series 3 Current Reduction Conversion Procedure
On the rear panel of the E1135C PDU is a panel, shown
in
on page 11-8, which indicates the
voltage, number of phases, and full load amps (FLA),
also called A
RMS
, for the PDU as it was originally
specified. After completing this procedure, the FLA
will be decreased to match the new power requirements.
Using this information, and the power option
requirement for your country, determine the power
option the PDU is configured for. If you are moving the
system to a different location, you may want to
reconfigure the system to a different power option.
See
on page 10-84 for the full load amps,
wire sizes, and breaker sizes after this procedure is
completed. Mark out the old value and add the new
value on the A
RMS
line when the upgrade is complete.