Installation and Configuration
BL
Example: Setting Continuous Current Switch Equation
Example: Setting Continuous Current Limits (BL20)
To set the continuous current limit to 5.5A:
5.5A Continuous RMS x 1.414 = 7.8A continuous peak
(7.8A continuous peak/20A max peak) x 100 = 39%.
Open switches 1 and 4; close switches 2 and 3.
www.aerotech.com
Chapter 2
13