Appendix D
Innovation Series Water Heaters
GF-128
Default Settings
USER MANUAL
OMM-0079_0B
07/21/11 AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
•
Ph: 800-526-0288
Page
101
of
200
APPENDIX D: WATER HEATER DEFAULT SETTINGS
MENU & OPTION
FACTORY DEFAULT
Setup Menu
Password
0
Language
English
Unit of Temp
Fahrenheit
Comm Address
0
Baud Rate
9600
Configuration Menu
Internal Setpt
130°F
Unit Type
Innovation WH
Unit Size
600, 800, 1060 MBH
Fuel Type
Natural Gas
Heater Mode
Constant Setpoint
Remote Signal
(If Heater Mode = Remote Setpoint)
4 – 20 mA ,/ 1-5V
Outdoor Sensor
Disabled
Setpt Lo Limit
60°F
Setpt Hi Limit
200°F
Temp Hi Limit
160°F
Max Valve Position
100%
Aux Start On Dly
0 sec
Failsafe Mode
Shutdown
mA Output
Off
Lo Fire Timer
2 sec.
Setpt Limiting
Disabled
Setpt Limit Band
0°F
Network Timeout
30 seconds
HI DB Setpt En
30
Demand Offset
0
Deadband High
0
Deadband Low
0