3.6
CONFIGURATION MENU
The Configuration Menu shown in Table 3-4 permits adjustment of the Internal Setpoint (Setpt)
temperature regardless of whether the valid password has been entered. Setpt is required for operation in
the Constant Setpoint mode. The remaining options in this menu require the valid password to be
entered, prior to changing existing entries. This menu contains a number of other configuration settings
which may or may not be displayed, depending on the current operating mode setting.
NOTE
The Configuration Menu settings shown in Table 3-4 are Factory-Set in accordance with
the requirements specified for each individual order. Therefore, under normal operating
conditions, no changes will be required.
Table 3-4. Configuration Menu
Available Choices or Limits
Menu Item Display
Minimum
Maximum
Default
Internal Setpt
Lo Temp
Limit
Hi Temp Limit
130°F
Unit Type
KC Boiler, KC Boiler LN,
BMK Boiler, BMK Boiler LN,
BMK Boiler Dual, KC Water
Heater, KC Water Heater LN,
INN
INN
Unit Size
0.5 MBTU, 1.0 MBTU
1.5 MBTU, 2.0 MBTU
3.0 MBTU, 3.5 MBTU
4.0 MBTU, 5.0 MBTU
6.0 MBTU
1.0 MBTU
Fuel Type
Natural Gas, Propane
Natural Gas
Water Heater Mode
Constant Setpoint,
Remote Setpoint,
Constant
Setpoint
Remote Signal
(If Mode = Remote
Setpoint, Direct Drive
or Combination)
4 – 20 mA/1 – 5V
0 -20 mA/0 – 5V
PWM Input (BMS)
Network
4 – 20 mA,
1-5V
Bldg Ref Temp
(If Mode = Outdoor
Reset)
40°F
230°F
70°F
Reset Ratio
(If Mode = Outdoor
Reset)
0.1
9.9
1.2
Outdoor Sensor
Enabled or Disabled
Disabled
System Start Tmp
(If Outdoor Sensor =
Enabled)
30°F
100°F
60°F