WATER HEATER DEFAULT SETTINGS - Continued
MENU & OPTION
FACTORY DEFAULT
Tuning Menu
Prop Band
8°F
Integral Gain
1.60
Derivative Time
0.10 min
Min Load Adj
0°F
Max Load Adj
0°F
FFWD Temp
N/A
Outlet Feedback
On
Feedback Gain
0.05
Breakpoint At 100%
83°F
Breakpoint At 90%
84°F
Breakpoint At 80%
85°F
Breakpoint At 70%
86°F
Breakpoint At 60%
87°F
Breakpoint At 50%
88°F
Breakpoint At 40%
92°F
Breakpoint At 30%
105°F
Breakpoint At 20%
124°F
Breakpoint At 10%
136°F
Breakpoint At 0%
138°F
Reset Defaults?