Ignition Switch Open During Ignition –
Continued
5. Initiate a unit start sequence.
6. The unit should begin its start sequence and then shut down and display
IGN SWITCH
OPEN DURING IGNITION
.
7. Replace the wire on the Ignition Switch and press the
CLEAR
button. The unit should
restart.
Figure 5-7. Typical Air/Fuel Valve Cover Location
Figure 5-8. Air/Fuel Valve Purge and Ignition Switch Locations
5.12 SAFETY PRESSURE RELIEF VALVE TEST
Test the safety Pressure Relief Valve in accordance with ASME Pressure Vessel Code, Section
VI.
AIR/FUEL VALVE
COVER
(Rotate CCW to remove)
Ignition Position
Switch
Purge Position
Switch
TO BLOWER
VALVE POSITION
DIAL
170
169
172
171
AIR/FUEL VALVE
SWITCH WIRING
BREAKOUT
AIR IN