APPENDIX A – INNOVATION MENU ITEM DESCRIPTIONS
MENU LEVEL & OPTION
DESCRIPTION
OPERATING MENU
Active Setpoint
This is the setpoint temperature to which the control is set
when operating in the Constant Setpoint or Remote Setpoint
Mode. When in the Constant Setpoint Mode, this value is
equal to the Internal Setpoint setting in the Configuration
Menu. When in the Remote Setpoint Mode, this value is the
setpoint equivalent to the remote analog signal supplied to
the unit
Air Temp
For monitoring purposes only
Outdoor Temp
Displayed only if outdoor sensor is installed and enabled.
Valve Position In
Desired input valve position. This would normally be the
same as the valve position shown on the bargraph when the
heater is operating.
Flame Strength
Displays flame strength from 0% to 100%.
Run Cycles
Displays the total number of run cycles from 0 to 999,999.
Run Hours
Displays total run time of unit in hours from 0 to 9,999,999.
Fault Log
Displays information on the last 20 faults (0 – 19).
SETUP MENU
Password
Allows password to be entered.
Once the valid password (159) is entered, options in the
Setup, Configuration and Tuning Menus can be modified.
Language
English only
Time
Displays time from 12:00 am to 11:59 pm.
Date
Displays dates from 01/01/00 to 12/31/99
Unit of Temp
Permits selection of temperature displays in degrees
Fahrenheit (°F) or degrees Celsius (°C). (Default = °F)
Comm Address
For RS-485 communications (0 to 127). Default address is 0.
RS-232 should have its own (programmable) password.
Baud Rate
Allows communications Baud Rate to be set (2400 to 19.2K).
(Default = 9600)
Software Version
Identifies the current software version of the control box (Ver
0.0 to Ver 9.9).