3.10 START/STOP LEVELS
The start and stop levels are the Air/Fuel Valve positions (% open) that start and stop the unit,
based on load. These levels are Factory preset as follows:
Start Level: 25%
Stop Level: 16%
Normally, these settings should not require adjustment.
Note that the energy input is not linearly related to the Air/Fuel Valve position. Refer to Table 3-
7 for the relationship between the energy input and Air/Fuel Valve position for a unit running on
natural gas.
Table 3-7. Relationship Between Air/Fuel Valve Position and Energy Input
For Units Running Natural Gas
Air/Fuel Valve
Position (%
Open)
Innovation Water Heater Model: Energy Input (BTU/Hr.)
INN600
INN800
INN1060
INN1350
16%
45,000
45,000
45,000
45,000
20%
87,000
97,000
97,000
181,000
30%
174,000
192,000
222,000
370,000
40%
243,000
330,000
416,000
665,000
50%
306,000
424,000
520,000
870,000
60%
370,000
486,000
715,000
1,001,000
80%
483,000
615,000
845,000
1,203,000
100%
600,000
800,000
1,060,000
1,350,000