![Aerco G-13-1854 Installation, Operation And Maintenance Manual Download Page 116](http://html.mh-extra.com/html/aerco/g-13-1854/g-13-1854_installation-operation-and-maintenance-manual_2861565116.webp)
Innovation Water Heaters Installation, Operation & Maintenance Manual
CHAPTER 9 – WATER HEATER MANAGEMENT
Page
116
of
196
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0078_0J
PRI: 11/22/2013
Phone: 800-526-0288
GF-128
WHM Programming & Start-Up Procedure
- Continued
11. Enter the desired value for the Nxt Off option. Press ENTER to store the selection.
12. Scroll to the
Lead/Lag
Hours
option (default = 72). If the desired setting for this option is
not displayed, press the CHANGE key.
13. Enter the desired value for the Lead/Lag Hours option. Press ENTER to store the
selection.
14. The WHM menu contains
Setback
options which are used to adjust the setpoint
temperature, start time and end time during periods of low DHW demand. These options
are selected as specified in steps 15 through 18 which follow.
15. To specify the setback temperature, scroll to the
Setback Setpoint
option (default =
130ºF). If this is not the desired setting, press the CHANGE key.
16. Enter the desired
Setback Setpoint
temperature. Press ENTER to store the selection.
17. Next, the
Setback Start
and
Setback End
time options must be specified (defaults =
12:00am for both options). To change each option scroll to
Setback Start
or
Setback End
and press the CHANGE key.
18. Separately enter the desired Start and End time (12:00am to 11:59pm). Press ENTER to
store each entry.
19. This completes the required entries for the WHM Master. All but two of the required menu
setting will be automatically be “pushed” to the WHM Slaves as they are brought on-line.
The options which are not “pushed” to each WHM Slave are:
•
Comm Address (in Setup menu)
•
WHM Mode
20. Enter the desired Comm Address and WHM Mode (WHM Slave) at the C-More Control
Panel for each of the WHM Slaves on the network.
21. After the required entries are made at each WHM Slave, check to ensure the REMOTE
LED on the C-More Control Panel for each unit in the WHM network is illuminated. When
illuminated, it indicates that the RS485 communications are operating properly.
22. The WHM menu contains two additional menu options which can be set at the WHM
Master. These options are
WHM Auto Mstr
and
WHM Auto Timer
. In order to view or
change these two options, the Level 2 Password (6817) must be entered as follows:
a. Press the MENU key on the front panel of the C-More and access the
Setup
Menu.
b. Scroll to the
Password
menu option and press the
CHANGE
key.
c. Enter 6817 and then press the ENTER key to store the password.
d. Press the MENU key on the C-More and scroll back to the
WHM
Menu.
23. Scroll to the
WHM Auto Mstr
option. The default value for this option is Off (disabled). If
you wish to enable this option, select
Yes
and then press the ENTER key to store the
setting.
24. If the
WHM Auto Mstr
option was set to
Yes
(enabled) in step 23, proceed to step 25. If
this option remains set to No (disabled), skip step 25 and go to step 27.