Benchmark 2500 - 3000 Boilers
CHAPTER 3 – OPERATION
Page
46
of
207
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0094_0F
09/30/2015
Ph.: 800-526-0288
GF-137
The Items contained in groups 2-5 are NOT DISPLAYED unless that particular item group has
been enabled from the C-More keypad.
Table 3-7: BST Menu
Menu Item Display
Available Choices or Limits
Default
Minimum
Maximum
1
BST Mode
Off
BST Slave
BST Master
Off
2
BST Setpoint
BST Setpt Lo Limit
BST Setpt Hi Limit
130°F (54.4°C)
3
Header Temp
NA
Header Temp (°F)
4
BST Fire Rate
0
100%
Fire rate %
5
BST Ave Fire Rate
0
100%
Avg Fire Rate %
6
BST Outdoor Temp
NA
Outdoor Temp (°F)
7
Units Available
0
8
Units Present
8
Units Ignited
0
8
Units firing
9
BST Valve State
0 (CLOSED)
1 (OPEN)
0
10
1 Comm Errors 8
0
9
0
11
1 BST Units 8
0 (see table)
0 (see table)
0
12
*BST SETUP MENU*
Disabled
Enabled
Disabled
13
BST Setpoint Mode
Constant Setpoint
Remote Setpoint
Outdoor Reset
Constant Setpt
14
Head Temp Source
Network
FFWD Temp
FFWD Temp
15
Header Temp Addr
0
255
240
16
Header Temp Point
0
255
14
17
BST Outdoor Sens
Disabled
Enabled
Disabled
18
Outdr Tmp Source
Outdoor Temp
Network
Outdoor Temp
19
Outdoor Tmp Addr
0
255
240
20
Outdoor Tmp Pnt
0
255
215
21
BST Remote Signal
4-20 mA/1-5 VDC;
0-20 mA/0-5
VDC;
Network
Network
22
BST Auto Mstr
No
Yes
NOTE! A Modbus temperature
transmitter must be installed in
conjunction with this feature.
No
23
BST Auto Timer
10 sec
120 sec
30 sec
24
Remote Intlk Use
Boiler Shutdown
System Shutdown
System Shutdown
25
One Boiler Mode
Off
On-Outlet
Temp
On-Avg Temp
Off
26
1 Blr Threshold
10
35
25
27
Setpoint Setback
Disable
Enable
Disable
28
Setback Setpoint
BST Setpt Lo Limit
BST Setpt HI Limit
130°F (54.4°C)
29
Setback Start
12:00am
11:59pm
12.00am
30
Setback End
12:00am
11:59pm
12.00am
31
Rate Threshold
1°F (0.55°C)
30°F (16.5°C)
15°F (8.25°C)