Benchmark 2500 - 3000 Boilers
CHAPTER 8 – TROUBLESHOOTING GUIDE
Page
116
of
207
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0094_0F
09/30/2015
Ph.: 800-526-0288
GF-137
TABLE 8-1: BOILER TROUBLESHOOTING – Continued
FAULT INDICATION
PROBABLE CAUSES
CORRECTIVE ACTION
SSOV
SWITCH OPEN
1.
Actuator not allowing for full
closure of gas valve.
2.
SSOV powered when it should
not be.
3.
Defective switch or Actuator.
4.
Incorrectly wired switch.
1.
Observe operation of the Safety Shut-Off Valve (SSOV)
through indicator on the Valve actuator and ensure that the
valve is fully and not partially closing.
2.
If the SSOV never closes, it may be powered continuously.
Close the gas supply and remove power from the unit.
Refer fault to qualified service personnel.
3.
Remove the electrical cover from the SSOV and check
switch continuity. If the switch does not show continuity
with the gas valve closed, either adjust or replace the
switch or actuator.
4.
Ensure that the SSOV Proof of Closure switch is correctly
wired.
STEPPER MOTOR
FAILURE
1.
Air/Fuel Valve out of calibration.
2.
Air/Fuel Valve unplugged.
3.
Loose wiring connection to the
stepper motor.
4.
Defective Air/Fuel Valve stepper
motor.
5.
Defective Power Supply Board or
fuse.
6.
Defective IGST Board.
1.
Refer to GF-112 (C-More O & M) and perform the Stepper
Feedback Calibration procedure in Section 6, section
6.2.1.
2.
Check that the Air/Fuel Valve is connected to the Control
Box.
3.
.Inspect for loose connections between the Air/Fuel Valve
motor and the wiring harness.
4.
Replace stepper motor.
5.
Check DS1 & DS2 LEDs on Power Supply Board. If they
are not steady ON, replace Power Supply Board.
6.
Check “Heartbeat” LED DS1 and verify it is blinking ON &
OFF every second. If not, replace IGST Board.