Benchmark 2500 - 3000 Boilers
APPENDIX A: BOILER MENU DESCRIPTIONS
OMM-0094_0F
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
143
of
207
GF-137
Ph.: 800-526-0288
09/30/2015
Table A-5: Combustion Calibration Menu Item Descriptions
See section 3-8 for a range of choices and the default values.
NOTE
The Level 2 Password must be entered to view the options in the
Combustion Cal
menu. This menu is used during the Combustion
Calibration procedures described in Chapter 4 of this Manual.
COMBUSTION CAL MENU
MENU OPTION
DESCRIPTION
1
CAL Voltage 14%
Displays the default DC drive voltage provided to the blower
at each of the Air/Fuel Valve positions show in the left-hand
column. This drive voltage adjusts the rotational speed of the
blower to maximize combustion efficiency.
2
CAL Voltage 30%
3
CAL Voltage 45%
4
CAL Voltage 65%
5
CAL Voltage 85%
6
CAL Voltage 100%
7
Set Valve Position
Permits selection of the Air/Fuel Valve position (% open) to be
set from 0 to 100%.
8
Blower Output
Permits the DC drive voltage to the blower to be monitored.
9
Set Stby V out
Permits the Standby Voltage to be set from 0 to 4.00 Volts.
10
Oxygen Level
Permits the combustion oxygen level to be displayed (0% to
25%)