Benchmark 2500 - 3000 Boilers
APPENDIX B: STARTUP, STATUS & DISPLAY MESSAGES
OMM-0094_0F
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
145
of
207
GF-137
Ph.: 800-526-0288
09/30/2015
APPENDIX B:
STARTUP, STATUS & DISPLAY MESSAGES
Table B-1: Startup and Status Messages
MESSAGE
DESCRIPTION
DEMAND DELAY
XX sec
Displayed if Demand Delay is active.
DISABLED
HH:MM pm, pm
MM/DD/YY
Displayed if ON/OFF switch is set to
OFF
. The display also
shows the time (am or pm) and date that the unit was
disabled.
FLAME PROVEN
Displayed after flame has been detected for a period of 2
seconds. Initially, the flame strength is shown in %. After 5
seconds has elapsed, the time and date are shown in place
of flame strength.
IGNITION TRIAL
XX sec
Displayed during ignition trial of startup sequence. The
duration of cycle counts up in seconds.
PURGING
XX sec
Displayed during the purge cycle during startup. The
duration of the purge cycle counts up in seconds.
STANDBY
Displayed when ON/OFF switch is in the
ON
position, but
there is no demand for heat. The time and date are also
displayed.
WAIT
Prompts the operator to wait.
WARMUP
XX sec
Displayed for 2 minutes during the initial warm-up only.