Change Log
Date
Description
Changed By
03/20/2014
Rev E PIRs:
780
: replaced mechanical latch with magnetic
934-14
: Corrected labels of Blower Proof and Blocked Inlet switches in diagrams in chapter 7
942
: Replaced 460 V Power Box label in section 2-9.
934-24
: Increased max height of housekeeping pad to 8 inch (Chapter 2)
981
: Modified formatting of Table A in Appendix F – Part List
960:
Addition of two sub-sections in 2.10.12; addition of section 2.15-Sequencing Valve
Installation; addition of section 3.9 -BST Menu; addition of Chapter 10 – Boiler Sequencing
Technology; replaced all wiring schematics in Appendix J, addition of 24V Sequencing Valve.
934-33
: Modified step 13 in Combustion Calibration regarding defective O
2
Sensor.
934-37
: Modified Blocked Inlet switch Test instructions, section 6.8.2.
1005:
Changed 12 Month Maintenance Kit part number to 58025-01
Curtis Harvey
&
Chris Blair
09/30/2015
Rev F PIRs:
934-52
: Clarified electrical requirements in section 2.9.1, and external gas regulator in
section 2.8.3
900-11
: Changed torque in section 7.6 Burner Assembly Inspection, step 15, from 22 to 35.
979:
Updated gas train 22211 & 22173 in Appendix I.
992-1
: Replaced old style Condensate trap 20460 with new style, 24441 in section 7.7
1000
: P/N 61026 now labeled “Lean Oxygen Sensor,” 64081 now named “ECU”
1011
: Changed Blocked Inlet switch pressure from -8.0 to -4.5 in Appendix A.
934-65
: Added explanatory paragraph to section 2.15 – Sequencing Isolation Valve
Installation
1028
: Replace fuel rod 66020 with 66034
934-79
: Warranty revision, dated 6/11/14, replaced “water heater” with “boiler.”
934-87
: Updated graphic & instructions in section 2-10, updated tables 3-2, 3-3 and 3-4
934-99
: Added new section 7.9 - LWCO Cap Test Instructions
1092
: Removed Chapter 9 – RS232 Communication, per Firmware version 4.0 and above.
1094:
Replaced Tridicator P/N 69087-TAB with 123675-TAB.
934-145
: Warranty pages removed. Warranty information for all BMK units is now included in
a new stand-alone document, All Benchmark Limited Warranty, posted on the AERCO web
site.
934-150
: Clarified references to & function of spark monitor (p/n 61034) (or AC current
transducer) in section 2.10.4, added new section 7.13 Spark Monitor
934-155:
Added Installation Notes regarding BST with ProtoNode SSD to new section 9.1.
DIR 199
: Replaced sections 2.12.1 & 2.12.2 with statement about opening size of not less
than one square inch for each 4000 BTUs input for each unit.
1117:
Add 2
nd
intake nozzle, section 2.5, Fig. 2-3
1152:
Replace Thermowell 93359 with 58132
DIR 225
: Section 7.9, replaced "use WD_40" with "use K&N® Air Filter Oil (or equivalent).
Do NOT use WD-40."
1167-2
: Modified gas trains and schematics in Appendix H and I.
Chris Blair