CHAPTER 6 – SAFETY DEVICE TESTING
Page
74
of
207
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0094_0F
09/30/2015
Ph.: 800-526-0288
GF-137
6.2 LOW GAS PRESSURE FAULT TEST
Refer to Figure 6-1a and 6-1b then ensure that the leak detection ball valve located at the
Low
Gas Pressure
switch is closed.
Figure 6-1a:
BMK 2500:
Low Gas Pressure Test
Figure 6-1b:
BMK 3000:
Low Gas Pressure Test
NATURAL
GAS INLET
SSOV
TO
AIR/FUEL
VALVE
HIGH GAS
PRESSURE
SWITCH
LOW GAS
PRESSURE
SWITCH
MANUAL
SHUT-OFF
VALVE
1/4” NPT PLUG
And Ball Valve
(install
manometer here
for LOW GAS
PRESSURE
FAULT TEST
NATURAL
GAS INLET
SSOV
TO
AIR/FUEL
VALVE
HIGH GAS
PRESSURE
SWITCH
LOW GAS
PRESSURE
SWITCH
MANUAL
SHUT-OFF
VALVE
1/4” NPT PLUG
And Ball Valve
(install
manometer here
for LOW GAS
PRESSURE
FAULT TEST
LOW GAS BALL VALVE
LOW GAS BALL VALVE