INSTALLATION
2-3
the insulated metal flex hose on the hot water
supply outlet of the boiler. In order to install the
water supply piping, this rod must be removed
as follows:
1. Refer to Figure 2-3 and back off the hex nut
on the outlet side of the flex hose.
2. Next, disconnect the coupling nut from the
flange stud.
3. Completely remove the threaded rod, hex
piping connections. The physical location of the
supply and return piping connections are on the
rear of the unit as shown in Figure 2-4. Refer to
Appendix F, Drawing AP-A-811 for additional
dimensional data.
BOILER SUPPLY
4" – 150# FLANGED
CONNECTION
BOILER RETURN
nut and coupling nut from the boiler.
EXHAUST
MANIFOLD
4" – 150# FLANGED
CONNECTION
SHELL DRAIN
VALVE
2" GAS INLET
CONNECTION
PARTIAL TOP VIEW - REAR
Figure 2-3
REAR VIEW
Figure 2-4
Supply and Return Locations
2.6 CONDENSATE DRAINS
Location of Threaded Support Rod
IMPORTANT
THE INSULATED FLEX HOSE SHOWN IN
FIGURE 2-3 MUST BE LEVEL
OR
SLOPING UPWARD AS IT EXITS THE
BOILER.
FAILURE
TO
PROPERLY
POSITION THIS HOSE MAY CAUSE
INEFFECTIVE
AIR
ELIMINATION
RESULTING
IN
ELE-
VATED
TEMPERATURES
THAT
COULD
COMPROMISE THE TOP HEAD GASKET.
2.4.4 Removal of Strap and Packing
Material From Heat Exchanger
Prior to connecting the external gas supply or
electrical power to the unit. the strap and
packing material must be removed from the top of
the primary heat exchanger. This material is
located in the area of the ignitor-injector and staged
ignition solenoid on the burner assembly This can
be easily accomplished by removing the top panel
nearest to the front of the unit.
2.5 SUPPLY AND RETURN PIPING
The Benchmark 3.0 Boiler utilizes 4” 150#
flanges for the water system supply and return
The Benchmark 3.0 Boiler is designed to
condense water vapor from the flue products.
Therefore, the installation must have provisions
for suitable condensate drainage or collection.
Two condensate drain connections are provided
on the rear of the unit as shown in Figure 2-5.
One drain connection is located on the exhaust
manifold and the other is located on the
connecting manifold.
The drain at the bottom of the exhaust manifold
also includes a condensate trap containing a
float assembly. When condensate collects in the
exhaust manifold, the float rises, thereby
allowing it to discharge through the drain
opening. The drain pipe located on the
connecting manifold must be connected to a
second condensate trap which is packed
separately within the unit’s shipping container.
The procedures to install and connect both of
the
condensate drains
are
provided
in
paragraphs 2.6.1 and 2.6.2.
Summary of Contents for Benchmark 3.0LN Series
Page 6: ...iv ...
Page 8: ...B ...
Page 42: ...INITIAL START UP 4 8 ...
Page 80: ...A 6 ...
Page 84: ...B 4 ...
Page 86: ...C 2 APPENDIX C ...
Page 93: ...APPENDIX F APPENDIX F F 1 ...
Page 94: ...APPENDIX F F 2 ...
Page 95: ...APPENDIX F F 3 ...
Page 96: ...APPENDIX F F 4 ...
Page 97: ...APPENDIX F F 5 ...
Page 98: ...APPENDIX F F 6 ...
Page 99: ...APPENDIX F F 7 66034 ...
Page 100: ...APPENDIX F F 8 ...
Page 101: ...APPENDIX F F 9 ...
Page 102: ...APPENDIX F F 10 ...
Page 103: ...APPENDIX F F 11 ...
Page 104: ...APPENDIX F F 12 ...
Page 105: ...APPENDIX F F 13 ...
Page 106: ...APPENDIX F F 14 ...
Page 107: ...APPENDIX G APPENDIX G G 1 ...
Page 108: ...APPENDIX G G 2 ...
Page 109: ...APPENDIX G G 3 ...
Page 110: ...APPENDIX G G 4 ...
Page 111: ...APPENDIX G G 5 ...
Page 112: ...APPENDIX G G 6 ...
Page 113: ...APPENDIX H APPENDIX H H 1 ...
Page 114: ...APPENDIX H H2 ...
Page 115: ...APPENDIX H H 3 ...
Page 116: ...APPENDIX H H 4 ...
Page 117: ...APPENDIX H H 5 ...
Page 118: ...APPENDIX H H 6 ...
Page 119: ...APPENDIX H H 7 ...
Page 120: ...APPENDIX H H 8 ...
Page 122: ...APPENDIX I I 2 ...
Page 126: ...NOTES ...