MAINTENANCE
7-1
CHAPTER 7 MAINTENANCE
7.1 MAINTENANCE SCHEDULE
The unit requires regular routine maintenance to
keep up efficiency and reliability. For best
operation and life of the unit, the following
routine maintenance procedures should be
carried out in the time periods specified in Table
7-1. See Appendix I for a complete CSD-1
inspection check list.
In order to perform the maintenance tasks
specified in Table 7-1, the following
maintenance kits are available through your
local AERCO Sales Representative:
•
Annual Maintenance Kit, Part No. 58025-01
•
24-Month Waterside/Fireside Inspection Kit,
Part No. 58025-04 (See NOTE below)
NOTE
The 24-Month Waterside/Fireside Inspec-
tion Kit also includes the items contained
in the Annual Maintenance Kit. Therefore,
only Kit Part No. 58025-04 is required
when performing the waterside/fireside
inspections.
7.2 IGNITOR-INJECTOR
The ignitor-injector (part no. 58023) is located in
the body of the burner (see Figure 7-1). In
addition to providing the ignition spark required
to light the burner, this component also contains
a gas injector tube which connects to the staged
ignition assembly. The ignitor-injector may be
hot, therefore, care should be exercised to avoid
burns. It is easier to remove the ignitor-injector
from the unit after the unit has cooled to room
temperature.
BURNER
HOUSING
STAGED
IGNITION
ASSY
Appendix K contains recommended spare parts
lists for maintenance of the boiler.
IGNITOR-
INJECTOR
Figure 7-1.
FLAME DETECTOR
& GASKET (SECURED
WITH 2 SCREWS)
WARNING
TO AVOID PERSONAL INJURY,
PRIOR TO SERVICING:
•
DISCONNECT THE AC SUPPLY BY
TURNING
OFF
THE
SERVICE
SWITCH AND AC SUPPLY CIRCUIT
BREAKER.
•
SHUT OFF THE GAS SUPPLY AT
THE MANUAL SHUT-OFF VALVE
PROVIDED WITH THE UNIT
•
ALLOW THE UNIT TO COOL TO A
SAFE WATER TEMPERATURE TO
PREVENT BURNING OR SCALDING
Burner Assembly – Top View
To inspect/replace the Ignitor-injector, proceed
as follows:
1. Set the
ON/OFF
switch on the control panel,
to the
OFF
position. Disconnect AC power
from the unit
2. Remove the top and side panels from the
unit.
3. Disconnect the cable from the ignitor-injector.
4. Using a 7/16” open-end wrench, disconnect
the compression nut securing the gas injector
tube of the ignitor-injector to the elbow of the
staged ignition assembly. Disconnect the
staged ignition assembly from the ignitor-
injector.
Summary of Contents for Benchmark 3.0LN Series
Page 6: ...iv ...
Page 8: ...B ...
Page 42: ...INITIAL START UP 4 8 ...
Page 80: ...A 6 ...
Page 84: ...B 4 ...
Page 86: ...C 2 APPENDIX C ...
Page 93: ...APPENDIX F APPENDIX F F 1 ...
Page 94: ...APPENDIX F F 2 ...
Page 95: ...APPENDIX F F 3 ...
Page 96: ...APPENDIX F F 4 ...
Page 97: ...APPENDIX F F 5 ...
Page 98: ...APPENDIX F F 6 ...
Page 99: ...APPENDIX F F 7 66034 ...
Page 100: ...APPENDIX F F 8 ...
Page 101: ...APPENDIX F F 9 ...
Page 102: ...APPENDIX F F 10 ...
Page 103: ...APPENDIX F F 11 ...
Page 104: ...APPENDIX F F 12 ...
Page 105: ...APPENDIX F F 13 ...
Page 106: ...APPENDIX F F 14 ...
Page 107: ...APPENDIX G APPENDIX G G 1 ...
Page 108: ...APPENDIX G G 2 ...
Page 109: ...APPENDIX G G 3 ...
Page 110: ...APPENDIX G G 4 ...
Page 111: ...APPENDIX G G 5 ...
Page 112: ...APPENDIX G G 6 ...
Page 113: ...APPENDIX H APPENDIX H H 1 ...
Page 114: ...APPENDIX H H2 ...
Page 115: ...APPENDIX H H 3 ...
Page 116: ...APPENDIX H H 4 ...
Page 117: ...APPENDIX H H 5 ...
Page 118: ...APPENDIX H H 6 ...
Page 119: ...APPENDIX H H 7 ...
Page 120: ...APPENDIX H H 8 ...
Page 122: ...APPENDIX I I 2 ...
Page 126: ...NOTES ...