4-5
INITIAL START-UP
37. Press the
▼ arrow key until
CAL Voltage
40%
is displayed.
38. Press the
CHANGE
key.
CAL Voltage 40%
will begin to flash.
39. The oxygen level at the 40% valve position
should be as shown below. Also, ensure that
the carbon monoxide (CO) and nitrogen
oxide (NOx) readings do not exceed the
values shown.
Combustion Oxygen Level at
40% Valve Position
Oxygen %
± 0.2
Carbon
Monoxide
NOx
7.8 %
<50 ppm
<20 ppm
40. If the oxygen level is not within the specified
range, adjust the level using the
▲ and ▼
arrow keys. This will adjust the output
voltage to the blower motor as indicated on
the display. Pressing the
▲ arrow key
increases the oxygen level and pressing the
▼ arrow key decreases the oxygen level.
41. Once the oxygen level is within the specified
range at 40%, press the
ENTER
key to store
the selected blower output voltage for the
40% valve position.
42. Press the
▲ arrow key until
SET Valve
Position
appears on the C-MORE display.
43. Press the
CHANGE
key.
SET
Valve Position
will begin to flash.
44. Press the
▼ arrow key until the
SET Valve
Position
reads
30%
, then press the
ENTER
key.
45. Press the
▼ arrow key until
CAL Voltage
30%
is displayed.
46. Press the
CHANGE
key.
CAL Voltage 30%
will begin to flash.
47. The oxygen level at the 30% Valve Position
should be as shown below. Also, ensure that
the carbon monoxide (CO) and nitrogen
oxide (NOx) readings do not exceed the
values shown.
Combustion Oxygen Level at
30% Valve Position
Oxygen %
± 0.2
Carbon
Monoxide
NOx
8.0 %
<50 ppm
<20 ppm
48. If the oxygen level is not within the specified
range, adjust the level using the
▲ and ▼
arrow keys. This will adjust the output
voltage to the blower motor as indicated on
the display. Pressing the
▲ arrow key
increases the oxygen level and pressing the
▼ arrow key decreases the oxygen level.
49. Once the oxygen level is within the specified
range at 30%, press the
ENTER
key to store
the selected blower output voltage for the
30% valve position.
50. Press the
▲ arrow key until
SET Valve
Position
appears on the C-MORE display.
51. Press the
CHANGE
key.
SET Valve Position
will begin to flash.
52. Press the
▼ arrow key until the
SET Valve
Position
reads
14%
, then press the
ENTER
key.
53. Press the
▼ arrow key until
CAL Voltage
14%
is displayed.
54. Press the
CHANGE
key.
CAL Voltage 14%
will begin to flash.
55. The oxygen level at the 14% Valve Position
should be as shown below. Also, ensure that
the carbon monoxide (CO) and nitrogen
oxide (NOx) readings do not exceed the
values shown.
Combustion Oxygen Level at
14% Valve Position
Oxygen %
± 0.2
Carbon
Monoxide
NOx
8.5 %
<50 ppm
<30 ppm
56. If the oxygen level is not within the specified
range, adjust the level using the
▲ and ▼
arrow keys. This will adjust the output
voltage to the blower motor as indicated on
the display. Pressing the
▲ arrow key
increases the oxygen level and pressing the
▼ arrow key decreases the oxygen level.
57. Once the oxygen level is within the specified
range at 14%, press the
ENTER
key to store
the selected blower output voltage for 14%
Valve Position.
IMPORTANT
Repeat steps 18 through 57 until the
blower output voltage does not require
adjustment when sequencing from 70% to
14%.
58. This completes the natural gas combustion
calibration procedure.
Summary of Contents for Benchmark 3.0LN Series
Page 6: ...iv ...
Page 8: ...B ...
Page 42: ...INITIAL START UP 4 8 ...
Page 80: ...A 6 ...
Page 84: ...B 4 ...
Page 86: ...C 2 APPENDIX C ...
Page 93: ...APPENDIX F APPENDIX F F 1 ...
Page 94: ...APPENDIX F F 2 ...
Page 95: ...APPENDIX F F 3 ...
Page 96: ...APPENDIX F F 4 ...
Page 97: ...APPENDIX F F 5 ...
Page 98: ...APPENDIX F F 6 ...
Page 99: ...APPENDIX F F 7 66034 ...
Page 100: ...APPENDIX F F 8 ...
Page 101: ...APPENDIX F F 9 ...
Page 102: ...APPENDIX F F 10 ...
Page 103: ...APPENDIX F F 11 ...
Page 104: ...APPENDIX F F 12 ...
Page 105: ...APPENDIX F F 13 ...
Page 106: ...APPENDIX F F 14 ...
Page 107: ...APPENDIX G APPENDIX G G 1 ...
Page 108: ...APPENDIX G G 2 ...
Page 109: ...APPENDIX G G 3 ...
Page 110: ...APPENDIX G G 4 ...
Page 111: ...APPENDIX G G 5 ...
Page 112: ...APPENDIX G G 6 ...
Page 113: ...APPENDIX H APPENDIX H H 1 ...
Page 114: ...APPENDIX H H2 ...
Page 115: ...APPENDIX H H 3 ...
Page 116: ...APPENDIX H H 4 ...
Page 117: ...APPENDIX H H 5 ...
Page 118: ...APPENDIX H H 6 ...
Page 119: ...APPENDIX H H 7 ...
Page 120: ...APPENDIX H H 8 ...
Page 122: ...APPENDIX I I 2 ...
Page 126: ...NOTES ...