4-4
INITIAL START-UP
NOTE
The remaining combustion calibration steps are
performed using the
Combustion Cal Menu
included in the C-More Control System. The
combustion calibration control functions will be
used to adjust the oxygen level (%) at air/fuel
valve positions of 70%, 50%, 45%, 30% and
14% as described in the following steps. These
steps assume that the inlet air temperature is
within the range of 50°F to 100°F.
16. Press the
MENU
Key on the front panel of
the C-MORE and access the
Setup
menu.
Enter password 6817 and then press the
ENTER
key.
17. Press the
MENU
Key on the front panel of
the C-MORE until
Combustion Cal Menu
appears on the C-More display.
18. Press the
▲ arrow key until
SET Valve
Position
appears on the C-MORE display.
19. Press the
CHANGE
key.
SET Valve Position
will begin to flash.
20. Press the
▲ arrow key until the
SET Valve
Position
reads
70%
. Press the
ENTER
key.
21. Next, press the down (
▼) arrow key until
CAL Voltage 70%
is displayed.
22. Press the
CHANGE
key and observe that
CAL Voltage 70%
is flashing.
23. The oxygen level at the 70% valve position
should be as shown below. Also, ensure that
the carbon monoxide (CO) and nitrogen
oxide (NOx) readings do not exceed the
values shown.
Combustion Oxygen Level at
70% Valve Position
Oxygen %
± 0.2
Carbon
Monoxide
NOx
6.0 %
<100 ppm
<30 ppm
24. If the oxygen level is not within the specified
range, adjust the level using the
▲ and ▼
arrow keys. This will adjust the output
voltage to the blower motor as indicated on
the display. Pressing the
▲ arrow key
increases the oxygen level and pressing the
down
▼ arrow key decreases the oxygen
level.
25. Once the oxygen level is within the specified
range at 70%, press the
ENTER
key to store
the selected blower output voltage for the
70% valve position.
NOTE
The remaining steps basically repeat the
procedures in steps 18 through 25 for air/fuel
valve positions of 50%, 40%, 30% and 14%
open. However, since oxygen levels vary, these
steps are repeated in their entirety. W hen
performing these steps, also ensure that the
carbon monoxide (CO) and nitrogen oxide (NOx)
readings do not exceed the values shown for
each valve position.
26. Press the
▲ arrow key until
SET Valve
Position
appears on the C-MORE display.
27. Press the
CHANGE
key.
SET Valve Position
will begin to flash.
28. Press the
▼ arrow key until the
SET Valve
Position
reads
50%
and then press the
ENTER
key.
29. Press the down
▼ arrow key until
CAL
Voltage 50%
is displayed.
30. Press the
CHANGE
key.
CAL Voltage 50%
will begin to flash.
31. The oxygen level at the 50% Valve Position
should be as shown below. Also, ensure that
the carbon monoxide (CO) and nitrogen
oxide (NOx) readings do not exceed the
values shown.
Combustion Oxygen Level at
50% Valve Position
Oxygen %
± 0.2
Carbon
Monoxide
NOx
7.0 %
<50 ppm
<20 ppm
32. If the oxygen level is not within the specified
range, adjust the level using the
▲ and ▼
arrow keys. This will adjust the output
voltage to the blower motor as indicated on
the display. Pressing the
▲ arrow key
increases the oxygen level and pressing the
▼ arrow key decreases the oxygen level.
33. Once the oxygen level is within the specified
range at 50%, press the
ENTER
key to store
the selected blower output voltage for the
50%
Valve Position
.
34. Press the
▲ arrow key until
SET Valve
Position
appears on the C-MORE display.
35. Press the
CHANGE
key.
SET Valve Position
will begin to flash.
36. Press the
▼ arrow key until the
SET Valve
Position
reads
40%
, then press the
ENTER
key.
Summary of Contents for Benchmark 3.0LN Series
Page 6: ...iv ...
Page 8: ...B ...
Page 42: ...INITIAL START UP 4 8 ...
Page 80: ...A 6 ...
Page 84: ...B 4 ...
Page 86: ...C 2 APPENDIX C ...
Page 93: ...APPENDIX F APPENDIX F F 1 ...
Page 94: ...APPENDIX F F 2 ...
Page 95: ...APPENDIX F F 3 ...
Page 96: ...APPENDIX F F 4 ...
Page 97: ...APPENDIX F F 5 ...
Page 98: ...APPENDIX F F 6 ...
Page 99: ...APPENDIX F F 7 66034 ...
Page 100: ...APPENDIX F F 8 ...
Page 101: ...APPENDIX F F 9 ...
Page 102: ...APPENDIX F F 10 ...
Page 103: ...APPENDIX F F 11 ...
Page 104: ...APPENDIX F F 12 ...
Page 105: ...APPENDIX F F 13 ...
Page 106: ...APPENDIX F F 14 ...
Page 107: ...APPENDIX G APPENDIX G G 1 ...
Page 108: ...APPENDIX G G 2 ...
Page 109: ...APPENDIX G G 3 ...
Page 110: ...APPENDIX G G 4 ...
Page 111: ...APPENDIX G G 5 ...
Page 112: ...APPENDIX G G 6 ...
Page 113: ...APPENDIX H APPENDIX H H 1 ...
Page 114: ...APPENDIX H H2 ...
Page 115: ...APPENDIX H H 3 ...
Page 116: ...APPENDIX H H 4 ...
Page 117: ...APPENDIX H H 5 ...
Page 118: ...APPENDIX H H 6 ...
Page 119: ...APPENDIX H H 7 ...
Page 120: ...APPENDIX H H 8 ...
Page 122: ...APPENDIX I I 2 ...
Page 126: ...NOTES ...